Operating Instructions—IFC-200 Operating Instructions 15
If a smoke detector is selected for verification, its alarm is ignored
during the verification time.
If an alarm from another point occurs while timing, the timer
deactivates and the alarm activates.
If the verification timer times out and an alarm still exist, the alarm
performs all standard functions.
If the verification timer times out and an alarm no longer exist, the
verification counter increments for this device, and returns to normal.
If an alarm exists from a monitor module point that has a Waterflow type
code, the ALARM SILENCE switch does not function.
Disabled input points do not cause an alarm or any control-by-event
activity. Disabled output points are held in the “Off” state. All disabled
points are treated as if they were in trouble, except that the status banner
reads DISABL.
Alarm
Verification Timer
(0-60 Seconds)
Waterflow
Circuits
Operation
Disable/Enable
Operation