BLOWER PERFORMANCE
All units employ direct-drive blower motors with
multiple speed taps available. The motors have
been selected to deliver the nominal air volume
against varying external static pressures when
necessary. After installation of the unit, it will be
necessary to check the air volume and change
the motor speed connection accordingly. All
units are factory-wired with the medium speed
winding connected.
A simple method for approximating sufficient air
volume is to measure the difference between the
supply and return air temperatures. In Heating
mode, the air temperature rise should be in the
range of 20ºF to 30ºF. In Cooling mode, the
temperature drop should be between 15ºF to
25ºF. If the values are outside the appropriate
range, increase or reduce the motor speed as
necessary.
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
007 260 180 Med BLU 260 250 235 205 185 160 130 - -
009 320 220 High BLK 385 375 360 335 295 260 220 - -
012
425 300 High
BLK
430 420 400 385 370 350 315 280 -
High BLK - - 860 850 820 775 705 600 465
Med BLU 745 735 710 685 655 615 560 500 -
Low RED 540 535 525 495 460 420 380 335 -
High
BLK
- 1060 1010 955 905 830 755 660 540
Med
BLU
900 870 840 800 760 705 650 560 -
Low RED 805 775 745 705 670 625 570 490 -
High BLK - 1170 1120 1075 1020 965 900 835 760
Med BLU 1000 970 945 905 860 820 780 725 655
Low
RED
855 820 785 750 710 670 630 590 -
High
BLK
- - 1540 1490 1435 1365 1285 1210 1110
Med BLU 1295 1275 1255 1240 1205 1160 1115 1060 990
Low RED 1190 1160 1145 1115 1085 1045 1000 940 850
High BLK - - 1710 1695 1675 1655 1610 1560 1505
Med
BLU
1400 1380 1355 1335 1305 1270 1245 1210 1170
Low RED 1165 1155 1140 1110 1080 1050 1010 965 930
High BLK - - - - 2000 1955 1900 1845 1780
Med BLU 1755 1745 1720 1690 1660 1630 1600 1555 1500
Low RED 1505 1490 1465 1435 1400 1365 1325 1280 1230
High
BLK
- - 2560 2530 2490 2440 2370 2300 2220
Med BLU - 2100 2085 2060 2035 2000 1960 1910 1870
Low RED 1905 1885 1860 1835 1805 1770 1730 1680 1620
High BLK - - 2560 2530 2490 2440 2370 2300 2220
Med BLU - 2100 2085 2060 2035 2000 1960 1910 1870
Low
RED
1905 1885 1860 1835 1805 1770 1730 1680 1620
Units are shipped pre-wired for Medium speed.
All airflow ratings are at lowest voltage rating of dual rating (ie. 208 volt)
Airflow ratings include resistance of wet coil and clean air filters.
070
External Static Pressure (in w.g.)
048
036
030
024
018
060
Rated
CFM
Unit Size
042
Motor
Speed
Min.
CFM
445
560
700
840
640
800
1000
Lead Wire
Color
2200 1400
980
1120
14002000
1600
1400
1200