6
INTRODUCTION
JCI ‘RSH’ and 'RSV' units are completely self
contained heating and air conditioning units. This
equipment employs a water-to-
exchanger to extract (heating cycle) or reject
(cooling c
ycle) heat from/to a circulating water
loop.
All models 1/2 through 6 tons are shipped as
factory-
charged packages. Horizontal (RSH)
units are designed for suspended ceiling
mounting, and are constructed with integral
hanger channels. Vertical (RSV) uni
designed for free-
standing floor mounting. All
units are shipped completely factory wired and
pre-
piped. Water supply, water outlet, and
condensate drain connections are via female
threaded pipe fittings.
Each refrigeration circuit includes an adj
bi-
flow expansion valve, liquid line filter drier, and
multiple service gauge ports. External high
pressure and low-
pressure protection switches
are included in each compressor circuit. A
standard suction line freezestat protects against
low evapor
ator temperatures, due to low water
supply temperatures. In the case when low water
temperature operation is required, freeze stat
protection can be disabled. Heat Pump models
feature a pilot operated, sliding piston type, 4
way reversing valve with a repl
solenoid coil.
JCI ‘RSH’ and 'RSV' units are completely self
-
contained heating and air conditioning units. This
exchanger to extract (heating cycle) or reject
ycle) heat from/to a circulating water
-
All models 1/2 through 6 tons are shipped as
charged packages. Horizontal (RSH)
units are designed for suspended ceiling
mounting, and are constructed with integral
hanger channels. Vertical (RSV) uni
ts are
standing floor mounting. All
units are shipped completely factory wired and
piped. Water supply, water outlet, and
condensate drain connections are via female
Each refrigeration circuit includes an adj
ustable
flow expansion valve, liquid line filter drier, and
multiple service gauge ports. External high
pressure protection switches
are included in each compressor circuit. A
standard suction line freezestat protects against
ator temperatures, due to low water
supply temperatures. In the case when low water
temperature operation is required, freeze stat
protection can be disabled. Heat Pump models
feature a pilot operated, sliding piston type, 4
-
The coaxial water-to-
refrigerant heat exchanger
and all water piping within the unit are rated for
water side working pressures up to 400 psig.
All units are completely factory wired with all
necessary operating controls, complete with
standard microprocessor control. A 24 volt
control circuit, with oversize transformer, is
provided for field connection. Units are designed
to operate with conventi
interface. The reversing valve solenoid coil shall
be energized in cooling mode only.
These units are designed for
only. They are not intended or
outdoor installation.
PERFORM INSTALLATION AND SERVICE
OF THIS EQUIPMENT.
-IOM2 (0611)
refrigerant heat exchanger
and all water piping within the unit are rated for
water side working pressures up to 400 psig.
All units are completely factory wired with all
necessary operating controls, complete with
standard microprocessor control. A 24 volt
control circuit, with oversize transformer, is
provided for field connection. Units are designed
interface. The reversing valve solenoid coil shall
be energized in cooling mode only.
installation
SHOULD
PERFORM INSTALLATION AND SERVICE