Hardware Installation S300-DIN-RDR2S Module
34 24-10239-413 Rev. A
This document contains confidential and proprietary information of Johnson Controls, Inc.
© 2010 Johnson Controls, Inc.
Input Point Calibration
Termination resistance ranges from 150ohm to 2000ohm (1200 Ohms
recommended). Calibration command is launched from the host. Inputs can only be
calibrated if proper external resistor network is connected and the input is in the
secure state. See “General Input Wiring” on page 15 for reference.
NC or
NO
Reader (Top)
Door Strike
Output is set every time an access
grant or auxiliary access occurs.
General Purpose Output 5
Output is logically mapped to
connector NO/NC (Top). It can be
timed, set, reset, fast flash, or slow
flash.
OUT21 Reader (Bottom)
Red Light Output
Output is set every time an access
de
ny occurs.
General Purpose Output OUT21
Output is logically mapped to
conn
ector OUT21. It can be timed,
set, reset, fast flash, or slow flash.
Output is an open collector that
switches to ground.
OUT22 Reader (Bottom)
Green Light Output
Output is set every time an access
grant occurs.
General Purpose Output OUT22
Output is logically mapped to
conn
ector OUT22. It can be timed,
set, reset, fast flash, or slow flash.
Output is an open collector that
switches to ground.
OUT23 Reader (Bottom)
Shunt Output
Output is set every time an access
grant or auxiliary access occurs.
General Purpose Output OUT23
Output is logically mapped to
conn
ector OUT23. It can be timed,
set, reset, fast flash, or slow flash.
Output is an open collector that
switches to ground.
OUT02 General Purpose Output OUT02
Output is logically mapped to
connector OUT02. It can be timed,
set, reset, fast flag, or slow flash.
Output is an open collector that
switches to ground.
General Purpose Output OUT02
Output is logically mapped to
connector OUT02. It can be timed,
set, reset, fast flag, or slow flash.
Output is an open collector that
switches to ground.
NC or
NO
Reader (Bottom)
Door Strike
Output is set every time an access
grant or auxiliary access occurs.
General Purpose Output NO/NC
(Bottom
)
Output is logically mapped to
conn
ector NO/NC (Bottom). It can be
timed, set, reset, fast flash, or slow
flash.
Table 6: Output Point Signals (CK722 Controllers)
Signal
Names
Reader Terminal Object
Defined
Reader Terminal Object NOT
Defined