Instructions for capacity control (AC mode for example)
Ts Leaving chilled water temperature setpoint (LEL TEMP SET )
D Differential of Leaving chilled water temperature (LEL TEMP CR)
DbDifferential buffering value
When leaving chilled water temperature (Ts + D), the compressor will load. when leaving chilled water
temperature (Ts - D) and(Ts + D) , the comrepssor will operate fuzzy control logic. when leaving chilled
water temperature (Ts D- Db) and(Ts - D) , the comrepssor will unload. When leaving chilled water
temperature (Ts D- Db) , the compressor will be cycling shut down.
By setting the value of Ts, D and Db, the temperature range of different running
mode(Hold/Unload/Load/Stop) of compressor can be adjusted.
Loading
Holding
Unloading
Emergency Stop
Low
temperature
High
temperature
Ts+D
Ts
Ts-D
Ts-D-Db
YEWS-E Water Cooling Screw Chiller/Heat Pump
32