Temperature
Resistance KΩ
Temperature
Resistance KΩ
-5
42.82
17
14.3
-3
38.53
19
13.1
-1
34.57
21
11.96
1
31.32
23
10.93
3
28.29
25
10
5
25.59
27
9.16
7
23.17
29
8.4
9
21.01
31
7.71
11
19.07
33
7.085
13
17.33
35
6.517
15
15.77
37
6
Discharge temperature sensor
Temperature
Resistance KΩ
Temperature
Resistance KΩ
0
166.75
33
35.272
3
142.9
36
31.076
6
122.81
39
27.44
9
105.83
42
24.283
12
91.443
45
21.535
15
79.219
48
19.137
18
68.804
51
17.042
21
59.908
54
15.206
24
52.291
57
13.595
27
45.752
60
12.178
30
40.125
63
10.929
9.2 Sensor Calibration Charts
Chilled leaving liquid temperature, chilled return liquid temperature, leaving cooling liquid temperature, returning
cooling liquid temperature sensors:
YEWS-E Water Cooling Screw Chiller/Heat Pump
64

Table of Contents