EasyManuals Logo

Johnson Controls YEWS Series User Manual

Johnson Controls YEWS Series
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #46 background imageLoading...
Page #46 background image
Items
LEL TEMP SET
LEL TEMP CE
LOW LELT
HIGH LCLT
LEP UNLOAD
LEP SHUT DOWN
HOLD LOAD D.P
UNLOAD D.P
HIGH D.P.SHUTDOWN
UNLOAD CURR.
DELTA T
Defult values
7.0
1.0
2.0
43.0
175KPa
165KPa
1030KPa
1060KPa
1090KPa
95%
3.5
Setting range
4.0~15.0
0.5~2.0
1.0~7.0
30.0~60.0
150.0~300.0 KPa
150.0~300.0 KPa
100.0~1300.0 KPa
100.0~1300.0 KPa
100.0~1350.0 KPa
10~98%
2.0~6.0
Access level
User password
User password
Service password
Service password
Service password
Service password
Service password
Service password
Service password
Service password
Service password
(2) Assignable parameters setting and defult values (AC mode)
(3) Assignable parameters setting and defult values (ITS mode)
Items
LEL TEMP SET
LEL TEMP CE
LOW LELT
CR BUFFER
HIGH LCLT
LEP UNLOAD
LEP SHUT DOWN
HOLD LOAD D.P
UNLOAD D.P
HIGH D.P.SHUTDOWN
UNLOAD CURR.
DELTA T
LISV TEMP
Setting range
-8.0~+5.0
0.5~2.0
-15.0~+5.0
1.0 2.5
30.0~60.0
80.0~300.0 KPa
80.0~300.0 KPa
100.0~1300.0 KPa
100.0~1300.0 KPa
100.0~1350.0 KPa
10~98%
2.0~6.0
50.0~80.0
Defult values
-5.6
1.0
2.0
2.5
43.0
175KPa
165KPa
1030KPa
1060KPa
1090KPa
95%
4.5
70.0
Access level
User password
User password
Service password
User password
Service password
Service password
Service password
Service password
Service password
Service password
Service password
Service password
Service password
YEWS-E Water Cooling Screw Chiller/Heat Pump
41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls YEWS Series and is the answer not in the manual?

Johnson Controls YEWS Series Specifications

General IconGeneral
BrandJohnson Controls
ModelYEWS Series
CategoryChiller
LanguageEnglish

Related product manuals