EasyManuals Logo

Johnson Controls York YCAL0014E Series User Manual

Johnson Controls York YCAL0014E Series
216 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #81 background imageLoading...
Page #81 background image
JOHNSON CONTROLS
81
FORM 150.62-NM6 (103)
The fourth message indicates what stage of condenser
fan operation is active. For YCAL0014 to YCAL0080 un-
less a low ambient kit is added, only stages 1 and 3 will
be used to cycle the condenser fans. However, stage
2 may be shown in this display without a low ambient
kit added, but it has no effect. YCAL0090 - YCAL0124
have 3 or 4 fan stages as standard.
See the section on Condenser Fan Control in the UNIT
OPERATION section for more information.
2
The fth message displays current as sensed by the
optional current feedback circuitry. The display reads
out in amps along with the DC feedback voltage from
the module. Current is calculated by
225AActual Volts
5 Volts
Individual displays will be present for each system, if
CURRENT FEEDBACK ONE PER SYSTEM is pro-
grammed under the OPTIONS Key. Combined com-
pressor current for each system is displayed.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls York YCAL0014E Series and is the answer not in the manual?

Johnson Controls York YCAL0014E Series Specifications

General IconGeneral
BrandJohnson Controls
ModelYork YCAL0014E Series
CategoryChiller
LanguageEnglish

Related product manuals