Table 3: Approximate unit weight including motor and 150 psig (1.14 MPa)
1
compact
waterboxes
Shells Compressor
Shipping, lb
(kg)
2
Operation weight,
lb (kg)
Est. refrigerant charge,
lb (kg)
3
Q-Q H9 41,309 (18,737) 54,860 (24,884) 4060 (1841)
R-R H9 46,740 (21,201) 59,674 (27,068) 5040 (2286)
B-L K1 74,800 (33,926) 92,500 (41,953) 5635 (2555)
M-M K2 83,200 (37,735) 104,100 (47,215) 6887 (3123)
N-B K2 84,200 (38,189) 105,100 (47,668) 6774 (3072)
E-C K3 116,600 (52,884) 147,100 (66,717) 10,600 (4808)
F-D K3
125,500 (56,921)
4
157,500 (71,434) 9224 (4183)
G-E K4
141,100 (63,996)
4
179,100 (81,231) 11,512 (5221)
H-F K4
139,000 (63,043)
4
176,300 (79,961) 10,836 (9414)
K-K K7
174,100 (78,963)
4
222,200 (100,779) 13,897 (6302)
1 Refer to product drawings for detailed weight information (Unit without starter).
2 Does not include refrigerant charge.
3 Refer to performance page for specific refrigerant charge, which will vary with a different tube diameter and different
shell size.
4 Unit shipped disassembled. Consult the performance page for individual weight.
Centrifugal Liquid Chillers20