Knocked-down unit component dimensions - evaporator
Figure 8: Evaporator section dimensions
Table 4: Evaporator section dimensions
Dimensions ft-in (mm)
Unit model compr/shells
A B C
H9/Q shells 16' 0" (4877) 6' 0" (1829) 7' 6" (2286)
H9/R shells 16' 0" (4877) 6' 4" (1930) 7' 9" (2362)
K1/B shells 18' 0" (5486) 6' 4" (1930) 8' 0" (2438)
K2/M shells 22' 0" ( 6706) 6' 4" (1930) 7' 10" (2388)
K2/N shells 18' 0" (5486) 6' 11" (2108) 8' 2" (2489)
K3/E shells 22' 0" (6706) 7' 9" (2362) 9' 0" (2743)
K3/F shells 18' 0" (5486) 8' 6" (2591) 9' 9" (2972)
K4/G shells 22' 0" (6706) 8' 6" (2591) 9' 9" (2972)
K4/H shells 18' 0" (5486) 9' 0" (2743) 10' 3" (3124)
K7/K shells 22' 0" (6706) 9' 0" (2743) 10' 3" (3124)
Note: For knocked-down shipment, add the associated dimension for compact or marine
waterboxes to the shells.