Table 90: ZY12 Charging Table System 2
Air Flow Indoor Db/Wb Outdoor DB Suction P Suction Temp. Liquid P Liquid Temp. Delta T Db Compr. amps
75 134 60 279 79 -26 8.4
85 135 59 327 88 -26 9.4300 Cfm/Ton 80/62
95 135 59 376 98 -27 10.3
75 135 60 279 79 -26 8.6
85 139 60 330 89 -25 9.5300 Cfm/Ton 80/67
95 142 60 381 99 -24 10.4
75 136 60 280 79 -26 8.8
85 143 61 332 89 -23 9.6300 Cfm/Ton 80/72
95 150 62 385 99 -20 10.5
75 128 57 278 78 -23 8.4
85 130 57 328 88 -23 9.4300 Cfm/Ton 75/62
95 132 57 377 98 -23 10.4
75 139 62 278 80 -23 8.4
85 141 62 328 89 -23 9.3400 Cfm/Ton 80/62
95 143 61 378 99 -23 10.2
75 141 62 280 79 -22 8.6
85 144 62 331 89 -22 9.5400 Cfm/Ton 80/67
95 147 63 381 98 -21 10.4
75 142 62 282 78 -22 8.7
85 147 63 333 88 -20 9.6400 Cfm/Ton 80/72
95 152 64 385 98 -19 10.5
75 134 59 278 79 -20 8.4
85 137 59 328 88 -20 9.3
400 Cfm/Ton 75/62
95 139 59 378 98 -19 10.3
INSTALLATION MANUAL ZY SERIES 3-10ton 60 Hertz R-410A 137
Johnson Controls Ducted Systems