Table 10: ZY04 to 12 Standard Static Indoor Blower - With Powered Convenience Outlet
Compressor 1 Compressor 2
Electric Heat Field
Installed Kit 2EK045*
4
Min Disconnect Rating
Min Disconnect Rating/ Pwr Exh
Size (Tons)
Nominal Unit Voltage
RLA LRA MCC RLA LRA MCC
OD Fan Motors (each)
Supply Blower Motor
Pwr Exh Motor
Pwr Conv Outlet
Model kW Stages Amps
1
MCA (Amps)
2,3
Min Fuse/ Breaker Size (Amps)
Max Fuse/ Breaker Size (Amps)
FLA LRA
MCA w/Pwr Exh (Amps)
Min Fuse/ Breaker Size w/ Pwr Exh (Amps)
Max Fuse/ Breaker Size w/ Pwr Exh (Amps)
FLA LRA
None - - - 44.7 45 50 47 212 46.9 50 50 50 222
11725 12 1 33.3 53.5 60 60 49 212 56.3 60 60 52 222
12525 18.6 1 51.6 76.4 80 80 70 212 79.1 80 80 73 222
13225 24 1 66.6 95.1 100 100 88 212 97.9 100 100 90 222
208-3-60 13.6 83.1 21 13.6 83.1 21 2.3 5.2 1.1 8.6
14225 31.8 2 88.3 122.3 125 125 112 212 125 150 150 115 222
None - - - 44.7 45 50 47 216 46.7 50 60 50 210
11725 16 1 38.5 60 60 60 55 216 62.5 70 70 58 210
12525 24.8 1 59.7 86.5 90 90 80 216 89 90 90 82 210
13225 32 1 77 108.1 110 110 99 216 110.6 125 125 102 210
230-3-60 13.6 83.1 21 13.6 83.1 21 2.3 5.2 1 8.6
14225 42.4 2 102 139.4 150 150 128 216 141.9 150 150 131 210
None - - - 21.1 25 25 23 108 22.1 25 25 24 105
11746 16.5 1 19.8 30.7 35 35 28 108 31.9 35 35 29 105
12846 27.8 1 33.4 47.7 50 50 44 108 48.9 50 50 45 105
13346 33 1 39.7 55.6 60 60 51 108 56.8 60 60 52 105
460-3-60 6.1 41 10 6.1 41 10 1.3 2.6 0.5 8.6
14246 41.7 2 50.2 68.7 70 70 63 108 69.9 70 70 64 105
None - - - 15.4 20 20 16 87 16.2 20 20 17 84
11758 17 1 16.4 25.2 30 30 23 87 26.2 30 30 24 84
08 (7.5)
575-3-60 4.2 33 7 4.2 33 7 1.1 2 0.4 8.6
13458 34 1 32.7 45.5 50 50 42 87 46.5 50 50 43 84
None - - - 44.9 45 50 48 212 47.1 50 50 50 222
11725 12 1 33.3 53.5 60 60 49 212 56.3 60 60 52 222
12525 18.6 1 51.6 76.4 80 80 70 212 79.1 80 80 73 222
13225 24 1 66.6 95.1 100 100 88 212 97.9 100 100 90 222
208-3-60 13.7 83.1 21 13.7 83.1 21 2.3 5.2 1.1 8.6
14225 31.8 2 88.3 122.3 125 125 112 212 125 150 150 115 222
None - - - 44.9 45 50 48 216 46.9 50 60 50 210
11725 16 1 38.5 60 60 60 55 216 62.5 70 70 58 210
12525 24.8 1 59.7 86.5 90 90 80 216 89 90 90 82 210
13225 32 1 77 108.1 110 110 99 216 110.6 125 125 102 210
230-3-60 13.7 83.1 21 13.7 83.1 21 2.3 5.2 1 8.6
14225 42.4 2 102 139.4 150 150 128 216 141.9 150 150 131 210
None - - - 21.4 25 25 23 108 22.4 25 25 24 105
11746 16.5 1 19.8 30.7 35 35 28 108 31.9 35 35 29 105
12846 27.8 1 33.4 47.7 50 50 44 108 48.9 50 50 45 105
13346 33 1 39.7 55.6 60 60 51 108 56.8 60 60 52 105
460-3-60 6.2 41 10 6.2 41 10 1.3 2.6 0.5 8.6
14246 41.7 2 50.2 68.7 70 70 63 108 69.9 70 70 64 105
None - - - 16.7 20 20 18 87 17.5 20 20 19 84
11758 17 1 16.4 25.2 30 30 23 87 26.2 30 30 24 84
09 (8.5)
575-3-60 4.8 33 8 4.8 33 8 1.1 2 0.4 8.6
13458 34 1 32.7 45.5 50 50 42 87 46.5 50 50 43 84
INSTALLATION MANUAL ZY SERIES 3-10ton 60 Hertz R-410A 37
Johnson Controls Ducted Systems

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls ZY Series and is the answer not in the manual?

Johnson Controls ZY Series Specifications

General IconGeneral
BrandJohnson Controls
ModelZY Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals