Table 10: ZY04 to 12 Standard Static Indoor Blower - With Powered Convenience Outlet
Compressor 1 Compressor 2
Electric Heat Field
Installed Kit 2EK045*
4
Min Disconnect Rating
Min Disconnect Rating/ Pwr Exh
Size (Tons)
Nominal Unit Voltage
RLA LRA MCC RLA LRA MCC
OD Fan Motors (each)
Supply Blower Motor
Pwr Exh Motor
Pwr Conv Outlet
Model kW Stages Amps
1
MCA (Amps)
2,3
Min Fuse/ Breaker Size (Amps)
Max Fuse/ Breaker Size (Amps)
FLA LRA
MCA w/Pwr Exh (Amps)
Min Fuse/ Breaker Size w/ Pwr Exh (Amps)
Max Fuse/ Breaker Size w/ Pwr Exh (Amps)
FLA LRA
None - - - 51.3 60 60 54 269 53.5 60 60 57 279
11725 12 1 33.3 53.5 60 60 54 269 56.3 60 60 57 279
12525 18.6 1 51.6 76.4 80 80 70 269 79.1 80 80 73 279
13225 24 1 66.6 95.1 100 100 88 269 97.9 100 100 90 279
208-3-60 16 110 25 16 110 25 5.8 5.2 1.1 8.6
14225 31.8 2 88.3 122.3 125 125 112 269 125 150 150 115 279
None - - - 50.7 60 60 54 268 52.7 60 60 56 273
11725 16 1 38.5 60 60 60 55 268 62.5 70 70 58 273
12525 24.8 1 59.7 86.5 90 90 80 268 89 90 90 82 273
13225 32 1 77 108.1 110 110 99 268 110.6 125 125 102 273
230-3-60 16 110 25 16 110 25 5.2 5.2 1 8.6
14225 42.4 2 102 139.4 150 150 128 268 141.9 150 150 131 273
None - - - 25.3 30 30 27 130 26.3 30 30 28 132
11746 16.5 1 19.8 30.7 35 35 28 130 31.9 35 35 29 132
12846 27.8 1 33.4 47.7 50 50 44 130 48.9 50 50 45 132
13346 33 1 39.7 55.6 60 60 51 130 56.8 60 60 52 132
460-3-60 7.8 52 12 7.8 52 12 2.9 2.6 0.5 8.6
14246 41.7 2 50.2 68.7 70 70 63 130 69.9 70 70 64 132
None - - - 18.7 20 20 20 101 19.5 20 20 21 103
11758 17 1 16.4 25.2 30 30 23 101 26.2 30 30 24 103
12 (10)
575-3-60 5.7 38.9 9 5.7 38.9 9 2.2 2 0.4 8.6
13458 34 1 32.7 45.5 50 50 42 101 46.5 50 50 43 103
With VFD
None - - - 37.9 40 50 39 210 40.1 45 50 41 215
10725 4.9 1 13.6 37.9 40 50 39 210 40.1 45 50 41 215
11725 12 1 33.3 55.8 60 60 51 210 58.5 60 60 54 215
208-3-60 17.6 136 27 2.3 7 1.1 8.6
12525 18.6 1 51.6 78.6 80 80 72 210 81.4 90 90 75 215
None - - - 38.1 40 50 39 212 40.1 45 50 41 217
10725 6.5 1 15.6 38.1 40 50 39 212 40.1 45 50 41 217
11725 16 1 38.5 62.5 70 70 58 212 65 70 70 60 217
230-3-60 17.6 136 27 2.3 7.2 1 8.6
12525 24.8 1 59.7 89 90 90 82 212 91.5 100 100 84 217
None - - - 19 20 25 19 105 20 20 25 21 107
10746 6 1 7.2 19 20 25 15 105 20 20 25 16 107
11746 16.5 1 19.8 31.9 35 35 29 105 33.2 35 35 31 107
460-3-60 8.5 66.1 13 1.3 3.6 0.5 8.6
12646 25.5 1 30.7 45.6 50 50 42 105 46.8 50 50 43 107
None - - - 14.3 15 20 15 79 15.1 20 20 16 81
11758 17 1 16.4 25.8 30 30 24 79 26.8 30 30 25 81
A7 (6)
575-3-60 6.3 55.3 10 1.1 2.5 0.4 8.6
12658 25.7 1 24.7 36.2 40 40 33 79 37.2 40 40 34 81
INSTALLATION MANUAL ZY SERIES 3-10ton 60 Hertz R-410A38
Johnson Controls Ducted Systems

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls ZY Series and is the answer not in the manual?

Johnson Controls ZY Series Specifications

General IconGeneral
BrandJohnson Controls
ModelZY Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals