EasyManuals Logo

Johnson Controls ZY Series User Manual

Johnson Controls ZY Series
144 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #43 background imageLoading...
Page #43 background image
Table 11: ZY04 to 12 Medium Static Indoor Blower - Without Powered Convenience Outlet
Compressor 1 Compressor 2
Electric Heat Field
Installed Kit 2EK045*
4
Min Disconnect Rating
Min Disconnect Rating/ Pwr Exh
Size (Tons)
Nominal Unit Voltage
RLA LRA MCC RLA LRA MCC
OD Fan Motors (each)
Supply Blower Motor
Pwr Exh Motor
Pwr Conv Outlet
Model kW Stages Amps
1
MCA (Amps)
2,3
Min Fuse/ Breaker Size (Amps)
Max Fuse/ Breaker Size (Amps)
FLA LRA
MCA w/Pwr Exh (Amps)
Min Fuse/ Breaker Size w/ Pwr Exh (Amps)
Max Fuse/ Breaker Size w/ Pwr Exh (Amps)
FLA LRA
None - - - 40.4 45 50 43 208 42.6 45 50 45 218
11725 12 1 33.3 48.1 50 50 44 208 50.9 60 60 47 218
12525 18.6 1 51.6 71 80 80 65 208 73.8 80 80 68 218
13225 24 1 66.6 89.8 90 90 83 208 92.5 100 100 85 218
208-3-60 13.6 83.1 21 13.6 83.1 21 2.3 5.2 1.1
14225 31.8 2 88.3 116.9 125 125 108 208 119.6 125 125 110 218
None - - - 40.4 45 50 43 211 42.4 45 50 45 206
11725 16 1 38.5 54.6 60 60 50 211 57.1 60 60 53 206
12525 24.8 1 59.7 81.1 90 90 75 211 83.6 90 90 77 206
13225 32 1 77 102.8 110 110 95 211 105.3 110 110 97 206
230-3-60 13.6 83.1 21 13.6 83.1 21 2.3 5.2 1
14225 42.4 2 102 134 150 150 123 211 136.5 150 150 126 206
None - - - 18.9 20 25 20 106 19.9 20 25 21 103
11746 16.5 1 19.8 28 30 30 26 106 29.3 30 30 27 103
12846 27.8 1 33.4 45 45 45 41 106 46.3 50 50 43 103
13346 33 1 39.7 52.9 60 60 49 106 54.1 60 60 50 103
460-3-60 6.1 41 10 6.1 41 10 1.3 2.6 0.5
14246 41.7 2 50.2 66 70 70 61 106 67.3 70 70 62 103
None - - - 13.7 15 15 14 85 14.5 15 15 15 83
11758 17 1 16.4 23 25 25 21 85 24 25 25 22 83
08 (7.5)
575-3-60 4.2 33 7 4.2 33 7 1.1 2 0.4
13458 34 1 32.7 43.4 45 45 40 85 44.4 45 45 41 83
None - - - 40.6 45 50 43 208 42.8 45 50 45 218
11725 12 1 33.3 48.1 50 50 44 208 50.9 60 60 47 218
12525 18.6 1 51.6 71 80 80 65 208 73.8 80 80 68 218
13225 24 1 66.6 89.8 90 90 83 208 92.5 100 100 85 218
208-3-60 13.7 83.1 21 13.7 83.1 21 2.3 5.2 1.1
14225 31.8 2 88.3 116.9 125 125 108 208 119.6 125 125 110 218
None - - - 40.6 45 50 43 211 42.6 45 50 45 206
11725 16 1 38.5 54.6 60 60 50 211 57.1 60 60 53 206
12525 24.8 1 59.7 81.1 90 90 75 211 83.6 90 90 77 206
13225 32 1 77 102.8 110 110 95 211 105.3 110 110 97 206
230-3-60 13.7 83.1 21 13.7 83.1 21 2.3 5.2 1
14225 42.4 2 102 134 150 150 123 211 136.5 150 150 126 206
None - - - 19.2 20 25 20 106 20.2 25 25 21 103
11746 16.5 1 19.8 28 30 30 26 106 29.3 30 30 27 103
12846 27.8 1 33.4 45 45 45 41 106 46.3 50 50 43 103
13346 33 1 39.7 52.9 60 60 49 106 54.1 60 60 50 103
460-3-60 6.2 41 10 6.2 41 10 1.3 2.6 0.5
14246 41.7 2 50.2 66 70 70 61 106 67.3 70 70 62 103
None - - - 15 20 20 16 85 15.8 20 20 17 83
11758 17 1 16.4 23 25 25 21 85 24 25 25 22 83
09 (8.5)
575-3-60 4.8 33 8 4.8 33 8 1.1 2 0.4
13458 34 1 32.7 43.4 45 45 40 85 44.4 45 45 41 83
INSTALLATION MANUAL ZY SERIES 3-10ton 60 Hertz R-410A 43
Johnson Controls Ducted Systems

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls ZY Series and is the answer not in the manual?

Johnson Controls ZY Series Specifications

General IconGeneral
BrandJohnson Controls
ModelZY Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals