Table 11: ZY04 to 12 Medium Static Indoor Blower - Without Powered Convenience Outlet
Compressor 1 Compressor 2
Electric Heat Field
Installed Kit 2EK045*
4
Min Disconnect Rating
Min Disconnect Rating/ Pwr Exh
Size (Tons)
Nominal Unit Voltage
RLA LRA MCC RLA LRA MCC
OD Fan Motors (each)
Supply Blower Motor
Pwr Exh Motor
Pwr Conv Outlet
Model kW Stages Amps
1
MCA (Amps)
2,3
Min Fuse/ Breaker Size (Amps)
Max Fuse/ Breaker Size (Amps)
FLA LRA
MCA w/Pwr Exh (Amps)
Min Fuse/ Breaker Size w/ Pwr Exh (Amps)
Max Fuse/ Breaker Size w/ Pwr Exh (Amps)
FLA LRA
None - - - 52 60 60 55 305 54.2 60 60 58 315
11725 12 1 33.3 54.4 60 60 55 305 57.1 60 60 58 315
12525 18.6 1 51.6 77.3 80 80 71 305 80 90 90 74 315
13225 24 1 66.6 96 100 100 88 305 98.8 100 100 91 315
208-3-60 16 110 25 16 110 25 5.8 10.2 1.1
14225 31.8 2 88.3 123.1 125 125 113 305 125.9 150 150 116 315
None - - - 51.4 60 60 55 308 53.4 60 60 57 313
11725 16 1 38.5 60.9 70 70 56 308 63.4 70 70 58 313
12525 24.8 1 59.7 87.4 90 90 80 308 89.9 90 90 83 313
13225 32 1 77 109 110 110 100 308 111.5 125 125 103 313
230-3-60 16 110 25 16 110 25 5.2 10.2 1
14225 42.4 2 102 140.3 150 150 129 308 142.8 150 150 131 313
None - - - 25.3 30 30 27 150 26.3 30 30 28 152
11746 16.5 1 19.8 30.8 35 35 28 150 32 35 35 29 152
12846 27.8 1 33.4 47.8 50 50 44 150 49 50 50 45 152
13346 33 1 39.7 55.6 60 60 51 150 56.9 60 60 52 152
460-3-60 7.8 52 12 7.8 52 12 2.9 4.8 0.5
14246 41.7 2 50.2 68.8 70 70 63 150 70 70 70 64 152
None - - - 18.4 20 20 20 117 19.2 20 20 20 119
11758 17 1 16.4 24.8 25 25 23 117 25.8 30 30 24 119
12 (10)
575-3-60 5.7 38.9 9 5.7 38.9 9 2.2 3.4 0.4
13458 34 1 32.7 45.1 50 50 42 117 46.1 50 50 42 119
With VFD
None - - - 35.5 40 50 36 207 37.7 40 50 38 212
10725 4.9 1 13.6 35.5 40 50 36 207 37.7 40 50 38 212
11725 12 1 33.3 52.8 60 60 49 207 55.5 60 60 51 212
208-3-60 17.6 136 27 2.3 8.9 1.1
12525 18.6 1 51.6 75.6 80 80 70 207 78.4 80 80 72 212
None - - - 34.8 35 50 35 215 36.8 40 50 37 220
10725 6.5 1 15.6 34.8 35 50 35 215 36.8 40 50 37 220
11725 16 1 38.5 58.4 60 60 54 215 60.9 70 70 56 220
230-3-60 17.6 136 27 2.3 8.2 1
12525 24.8 1 59.7 84.9 90 90 78 215 87.4 90 90 80 220
None - - - 17.3 20 25 17 106 18.3 20 25 19 109
10746 6 1 7.2 17.3 20 25 13 106 18.3 20 25 14 109
11746 16.5 1 19.8 29.9 30 30 27 106 31.1 35 35 29 109
460-3-60 8.5 66.1 13 1.3 4.1 0.5
12646 25.5 1 30.7 43.5 45 45 40 106 44.8 45 45 41 109
None - - - 13.3 15 15 13 86 14.1 15 15 14 88
11758 17 1 16.4 24.5 25 25 23 86 25.5 30 30 23 88
A7 (6)
575-3-60 6.3 55.3 10 1.1 3.2 0.4
12658 25.7 1 24.7 34.9 35 35 32 86 35.9 40 40 33 88
INSTALLATION MANUAL ZY SERIES 3-10ton 60 Hertz R-410A44
Johnson Controls Ducted Systems

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls ZY Series and is the answer not in the manual?

Johnson Controls ZY Series Specifications

General IconGeneral
BrandJohnson Controls
ModelZY Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals