Table 13: ZY04 to 12 High Static Indoor Blower - Without Powered Convenience Outlet
Compressor 1 Compressor 2
Electric Heat Field
Installed Kit 2EK045*
4
Min Disconnect Rating
Min Disconnect Rating/ Pwr Exh
Size (Tons)
Nominal Unit Voltage
RLA LRA MCC RLA LRA MCC
OD Fan Motors (each)
Supply Blower Motor
Pwr Exh Motor
Pwr Conv Outlet
Model kW Stages Amps
1
MCA (Amps)
2,3
Min Fuse/ Breaker Size (Amps)
Max Fuse/ Breaker Size (Amps)
FLA LRA
MCA w/Pwr Exh (Amps)
Min Fuse/ Breaker Size w/ Pwr Exh (Amps)
Max Fuse/ Breaker Size w/ Pwr Exh (Amps)
FLA LRA
None - - - 45.6 50 50 49 249 47.8 50 60 51 259
11725 12 1 33.3 54.4 60 60 50 249 57.1 60 60 53 259
12525 18.6 1 51.6 77.3 80 80 71 249 80 90 90 74 259
13225 24 1 66.6 96 100 100 88 249 98.8 100 100 91 259
208-3-60 13.7 83.1 21 13.7 83.1 21 2.3 10.2 1.1
14225 31.8 2 88.3 123.1 125 125 113 249 125.9 150 150 116 259
None - - - 45.6 50 50 49 255 47.6 50 60 51 250
11725 16 1 38.5 60.9 70 70 56 255 63.4 70 70 58 250
12525 24.8 1 59.7 87.4 90 90 80 255 89.9 90 90 83 250
13225 32 1 77 109 110 110 100 255 111.5 125 125 103 250
230-3-60 13.7 83.1 21 13.7 83.1 21 2.3 10.2 1
14225 42.4 2 102 140.3 150 150 129 255 142.8 150 150 131 250
None - - - 21.4 25 25 23 128 22.4 25 25 24 125
11746 16.5 1 19.8 30.8 35 35 28 128 32 35 35 29 125
12846 27.8 1 33.4 47.8 50 50 44 128 49 50 50 45 125
13346 33 1 39.7 55.6 60 60 51 128 56.9 60 60 52 125
460-3-60 6.2 41 10 6.2 41 10 1.3 4.8 0.5
14246 41.7 2 50.2 68.8 70 70 63 128 70 70 70 64 125
None - - - 16.4 20 20 17 103 17.2 20 20 18 100
11758 17 1 16.4 24.8 25 25 23 103 25.8 30 30 24 100
09 (8.5)
575-3-60 4.8 33 8 4.8 33 8 1.1 3.4 0.4
13458 34 1 32.7 45.1 50 50 42 103 46.1 50 50 42 100
None - - - 56.7 60 70 61 323 58.9 60 70 63 333
11725 12 1 33.3 60.3 70 70 61 323 63 70 70 63 333
12525 18.6 1 51.6 83.1 90 90 76 323 85.9 90 90 79 333
13225 24 1 66.6 101.9 110 110 94 323 104.6 110 110 96 333
208-3-60 16 110 25 16 110 25 5.8 14.9 1.1
14225 31.8 2 88.3 129 150 150 119 323 131.8 150 150 121 333
None - - - 56.2 60 70 60 322 58.2 60 70 62 327
11725 16 1 38.5 66.9 70 70 62 322 69.4 70 70 64 327
12525 24.8 1 59.7 93.4 100 100 86 322 95.9 100 100 88 327
13225 32 1 77 115 125 125 106 322 117.5 125 125 108 327
230-3-60 16 110 25 16 110 25 5.2 15 1
14225 42.4 2 102 146.3 150 150 135 322 148.8 150 150 137 327
None - - - 28 30 35 30 159 29 30 35 31 161
11746 16.5 1 19.8 34.1 35 35 31 159 35.4 40 40 33 161
12846 27.8 1 33.4 51.1 60 60 47 159 52.4 60 60 48 161
13346 33 1 39.7 59 60 60 54 159 60.3 70 70 55 161
460-3-60 7.8 52 12 7.8 52 12 2.9 7.5 0.5
14246 41.7 2 50.2 72.1 80 80 66 159 73.4 80 80 68 161
None - - - 20.6 25 25 22 124 21.4 25 25 23 126
11758 17 1 16.4 27.5 30 30 25 124 28.5 30 30 26 126
12 (10)
575-3-60 5.7 38.9 9 5.7 38.9 9 2.2 5.6 0.4
13458 34 1 32.7 47.9 50 50 44 124 48.9 50 50 45 126
1 Minimum Circuit Ampacity.
2 Dual Element, Time Delay Type.
3 HACR type per NEC.
4 Non-fused Disconnect. Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field
installed electric heat kits may exceed the factory installed disconnect amperage rating.
INSTALLATION MANUAL ZY SERIES 3-10ton 60 Hertz R-410A 55
Johnson Controls Ducted Systems

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls ZY Series and is the answer not in the manual?

Johnson Controls ZY Series Specifications

General IconGeneral
BrandJohnson Controls
ModelZY Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals