Table 14: ZY04 to 12 High Static Indoor Blower - Without Powered Convenience Outlet (with VFD)
Compressor 1 Compressor 2
Electric Heat Field
Installed Kit 2EK045*
4
Min Disconnect Rating
Min Disconnect Rating/ Pwr Exh
Size (Tons)
Nominal Unit Voltage
RLA LRA MCC RLA LRA MCC
OD Fan Motors (each)
Supply Blower Motor
Pwr Exh Motor
Pwr Conv Outlet
Model kW Stages Amps
1
MCA (Amps)
2,3
Min Fuse/ Breaker Size (Amps)
Max Fuse/ Breaker Size (Amps)
FLA LRA
MCA w/Pwr Exh (Amps)
Min Fuse/ Breaker Size w/ Pwr Exh (Amps)
Max Fuse/ Breaker Size w/ Pwr Exh (Amps)
FLA LRA
With VFD
None - - - 36.5 40 50 37 218 38.7 40 50 39 223
10725 4.9 1 13.6 36.5 40 50 37 218 38.7 40 50 39 223
11725 12 1 33.3 54 60 60 50 218 56.8 60 60 52 223
208-3-60 17.6 136 27 2.3 9.9 1.1
12525 18.6 1 51.6 76.9 80 80 71 218 79.6 80 80 73 223
None - - - 36 40 50 36 227 38 40 50 39 231
10725 6.5 1 15.6 36 40 50 36 227 38 40 50 39 231
11725 16 1 38.5 59.9 60 60 55 227 62.4 70 70 57 231
230-3-60 17.6 136 27 2.3 9.4 1
12525 24.8 1 59.7 86.4 90 90 79 227 88.9 90 90 82 231
None - - - 17.9 20 25 18 112 18.9 20 25 19 114
10746 6 1 7.2 17.9 20 25 14 112 18.9 20 25 15 114
11746 16.5 1 19.8 30.6 35 35 28 112 31.9 35 35 29 114
460-3-60 8.5 66.1 13 1.3 4.7 0.5
12646 25.5 1 30.7 44.3 45 45 41 112 45.5 50 50 42 114
None - - - 14.4 15 20 15 100 15.2 20 20 16 102
11758 17 1 16.4 25.9 30 30 24 100 26.9 30 30 25 102
A7 (6)
575-3-60 6.3 55.3 10 1.1 4.3 0.4
12658 25.7 1 24.7 36.3 40 40 33 100 37.3 40 40 34 102
None - - - 45.1 50 50 48 258 47.3 50 50 50 268
11725 12 1 33.3 54 60 60 50 258 56.8 60 60 52 268
12525 18.6 1 51.6 76.9 80 80 71 258 79.6 80 80 73 268
13225 24 1 66.6 95.6 100 100 88 258 98.4 100 100 91 268
208-3-60 13.6 83.1 21 13.6 83.1 21 2.3 9.9 1.1
14225 31.8 2 88.3 122.8 125 125 113 258 125.5 150 150 115 268
None - - - 44.6 45 50 47 267 46.6 50 60 50 261
11725 16 1 38.5 59.9 60 60 55 267 62.4 70 70 57 261
12525 24.8 1 59.7 86.4 90 90 79 267 88.9 90 90 82 261
13225 32 1 77 108 110 110 99 267 110.5 125 125 102 261
230-3-60 13.6 83.1 21 13.6 83.1 21 2.3 9.4 1
14225 42.4 2 102 139.3 150 150 128 267 141.8 150 150 130 261
None - - - 21 25 25 22 134 22 25 25 24 130
11746 16.5 1 19.8 30.6 35 35 28 134 31.9 35 35 29 130
12846 27.8 1 33.4 47.6 50 50 44 134 48.9 50 50 45 130
13346 33 1 39.7 55.5 60 60 51 134 56.8 60 60 52 130
460-3-60 6.1 41 10 6.1 41 10 1.3 4.7 0.5
14246 41.7 2 50.2 68.6 70 70 63 134 69.9 70 70 64 130
None - - - 16 20 20 17 115 16.8 20 20 18 113
11758 17 1 16.4 25.9 30 30 24 115 26.9 30 30 25 113
08 (7.5)
575-3-60 4.2 33 7 4.2 33 7 1.1 4.3 0.4
13458 34 1 32.7 46.3 50 50 43 115 47.3 50 50 43 113
INSTALLATION MANUAL ZY SERIES 3-10ton 60 Hertz R-410A56
Johnson Controls Ducted Systems

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls ZY Series and is the answer not in the manual?

Johnson Controls ZY Series Specifications

General IconGeneral
BrandJohnson Controls
ModelZY Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals