Table 14: ZY04 to 12 High Static Indoor Blower - Without Powered Convenience Outlet (with VFD)
Compressor 1 Compressor 2
Electric Heat Field
Installed Kit 2EK045*
4
Min Disconnect Rating
Min Disconnect Rating/ Pwr Exh
Size (Tons)
Nominal Unit Voltage
RLA LRA MCC RLA LRA MCC
OD Fan Motors (each)
Supply Blower Motor
Pwr Exh Motor
Pwr Conv Outlet
Model kW Stages Amps
1
MCA (Amps)
2,3
Min Fuse/ Breaker Size (Amps)
Max Fuse/ Breaker Size (Amps)
FLA LRA
MCA w/Pwr Exh (Amps)
Min Fuse/ Breaker Size w/ Pwr Exh (Amps)
Max Fuse/ Breaker Size w/ Pwr Exh (Amps)
FLA LRA
None - - - 45.3 50 50 48 258 47.5 50 60 51 268
11725 12 1 33.3 54 60 60 50 258 56.8 60 60 52 268
12525 18.6 1 51.6 76.9 80 80 71 258 79.6 80 80 73 268
13225 24 1 66.6 95.6 100 100 88 258 98.4 100 100 91 268
208-3-60 13.7 83.1 21 13.7 83.1 21 2.3 9.9 1.1
14225 31.8 2 88.3 122.8 125 125 113 258 125.5 150 150 115 268
None - - - 44.8 45 50 48 267 46.8 50 60 50 261
11725 16 1 38.5 59.9 60 60 55 267 62.4 70 70 57 261
12525 24.8 1 59.7 86.4 90 90 79 267 88.9 90 90 82 261
13225 32 1 77 108 110 110 99 267 110.5 125 125 102 261
230-3-60 13.7 83.1 21 13.7 83.1 21 2.3 9.4 1
14225 42.4 2 102 139.3 150 150 128 267 141.8 150 150 130 261
None - - - 21.3 25 25 23 134 22.3 25 25 24 130
11746 16.5 1 19.8 30.6 35 35 28 134 31.9 35 35 29 130
12846 27.8 1 33.4 47.6 50 50 44 134 48.9 50 50 45 130
13346 33 1 39.7 55.5 60 60 51 134 56.8 60 60 52 130
460-3-60 6.2 41 10 6.2 41 10 1.3 4.7 0.5
14246 41.7 2 50.2 68.6 70 70 63 134 69.9 70 70 64 130
None - - - 17.3 20 20 19 115 18.1 20 20 19 113
11758 17 1 16.4 25.9 30 30 24 115 26.9 30 30 25 113
09 (8.5)
575-3-60 4.8 33 8 4.8 33 8 1.1 4.3 0.4
13458 34 1 32.7 46.3 50 50 43 115 47.3 50 50 43 113
None - - - 55.3 60 70 59 345 57.5 60 70 62 355
11725 12 1 33.3 58.5 60 70 59 345 61.3 70 70 62 355
12525 18.6 1 51.6 81.4 90 90 75 345 84.1 90 90 77 355
13225 24 1 66.6 100.1 110 110 92 345 102.9 110 110 95 355
208-3-60 16 110 25 16 110 25 5.8 13.5 1.1
14225 31.8 2 88.3 127.3 150 150 117 345 130 150 150 120 355
None - - - 54.6 60 70 58 341 56.6 60 70 60 346
11725 16 1 38.5 64.9 70 70 60 341 67.4 70 70 62 346
12525 24.8 1 59.7 91.4 100 100 84 341 93.9 100 100 86 346
13225 32 1 77 113 125 125 104 341 115.5 125 125 106 346
230-3-60 16 110 25 16 110 25 5.2 13.4 1
14225 42.4 2 102 144.3 150 150 133 341 146.8 150 150 135 346
None - - - 27.2 30 30 29 166 28.2 30 30 30 168
11746 16.5 1 19.8 33.1 35 35 30 166 34.4 35 35 32 168
12846 27.8 1 33.4 50.1 60 60 46 166 51.4 60 60 47 168
13346 33 1 39.7 58 60 60 53 166 59.3 60 60 55 168
460-3-60 7.8 52 12 7.8 52 12 2.9 6.7 0.5
14246 41.7 2 50.2 71.1 80 80 65 166 72.4 80 80 67 168
None - - - 20.4 25 25 22 129 21.2 25 25 23 131
11758 17 1 16.4 27.3 30 30 25 129 28.3 30 30 26 131
12 (10)
575-3-60 5.7 38.9 9 5.7 38.9 9 2.2 5.4 0.4
13458 34 1 32.7 47.6 50 50 44 129 48.6 50 50 45 131
1 Minimum Circuit Ampacity.
2 Dual Element, Time Delay Type.
3 HACR type per NEC.
4 Non-fused Disconnect. Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field
installed electric heat kits may exceed the factory installed disconnect amperage rating.
INSTALLATION MANUAL ZY SERIES 3-10ton 60 Hertz R-410A 57