Table 15: ZY04 to 12 High Static Indoor Blower - With Powered Convenience Outlet
Compressor 1 Compressor 2
Electric Heat Field
Installed Kit 2EK045*
4
Min Disconnect Rating
Min Disconnect Rating/ Pwr Exh
Size (Tons)
Nominal Unit Voltage
RLA LRA MCC RLA LRA MCC
OD Fan Motors (each)
Supply Blower Motor
Pwr Exh Motor
Pwr Conv Outlet
Model kW Stages Amps
1
MCA (Amps)
2,3
Min Fuse/ Breaker Size (Amps)
Max Fuse/ Breaker Size (Amps)
FLA LRA
MCA w/Pwr Exh (Amps)
Min Fuse/ Breaker Size w/ Pwr Exh (Amps)
Max Fuse/ Breaker Size w/ Pwr Exh (Amps)
FLA LRA
None - - - 49.9 50 60 53 253 52.1 60 60 56 263
11725 12 1 33.3 59.8 60 60 55 253 62.5 70 70 58 263
12525 18.6 1 51.6 82.6 90 90 76 253 85.4 90 90 79 263
13225 24 1 66.6 101.4 110 110 93 253 104.1 110 110 96 263
208-3-60 13.7 83.1 21 13.7 83.1 21 2.3 10.2 1.1 8.6
14225 31.8 2 88.3 128.5 150 150 118 253 131.3 150 150 121 263
None - - - 49.9 50 60 53 260 51.9 60 60 56 254
11725 16 1 38.5 66.3 70 70 61 260 68.8 70 70 63 254
12525 24.8 1 59.7 92.8 100 100 85 260 95.3 100 100 88 254
13225 32 1 77 114.4 125 125 105 260 116.9 125 125 108 254
230-3-60 13.7 83.1 21 13.7 83.1 21 2.3 10.2 1 8.6
14225 42.4 2 102 145.6 150 150 134 260 148.1 150 150 136 254
None - - - 23.6 25 25 25 130 24.6 25 25 26 127
11746 16.5 1 19.8 33.4 35 35 31 130 34.7 35 35 32 127
12846 27.8 1 33.4 50.4 60 60 46 130 51.7 60 60 48 127
13346 33 1 39.7 58.3 60 60 54 130 59.6 60 60 55 127
460-3-60 6.2 41 10 6.2 41 10 1.3 4.8 0.5 8.6
14246 41.7 2 50.2 71.4 80 80 66 130 72.7 80 80 67 127
None - - - 18.1 20 20 19 105 18.9 20 20 20 102
11758 17 1 16.4 26.9 30 30 25 105 27.9 30 30 26 102
09 (8.5)
575-3-60 4.8 33 8 4.8 33 8 1.1 3.4 0.4 8.6
13458 34 1 32.7 47.3 50 50 43 105 48.3 50 50 44 102
None - - - 61 70 70 66 328 63.2 70 70 68 338
11725 12 1 33.3 65.6 70 70 66 328 68.4 70 70 68 338
12525 18.6 1 51.6 88.5 90 90 81 328 91.3 100 100 84 338
13225 24 1 66.6 107.3 110 110 99 328 110 125 125 101 338
208-3-60 16 110 25 16 110 25 5.8 14.9 1.1 8.6
14225 31.8 2 88.3 134.4 150 150 124 328 137.1 150 150 126 338
None - - - 60.5 70 70 65 326 62.5 70 70 67 331
11725 16 1 38.5 72.3 80 80 66 326 74.8 80 80 69 331
12525 24.8 1 59.7 98.8 100 100 91 326 101.3 110 110 93 331
13225 32 1 77 120.4 125 125 111 326 122.9 125 125 113 331
230-3-60 16 110 25 16 110 25 5.2 15 1 8.6
14225 42.4 2 102 151.6 175 175 139 326 154.1 175 175 142 331
None - - - 30.2 35 35 32 161 31.2 35 35 34 163
11746 16.5 1 19.8 36.8 40 40 34 161 38.1 40 40 35 163
12846 27.8 1 33.4 53.8 60 60 50 161 55.1 60 60 51 163
13346 33 1 39.7 61.7 70 70 57 161 62.9 70 70 58 163
460-3-60 7.8 52 12 7.8 52 12 2.9 7.5 0.5 8.6
14246 41.7 2 50.2 74.8 80 80 69 161 76.1 80 80 70 163
None - - - 22.3 25 25 24 126 23.1 25 25 25 128
11758 17 1 16.4 29.7 30 30 27 126 30.7 35 35 28 128
12 (10)
575-3-60 5.7 38.9 9 5.7 38.9 9 2.2 5.6 0.4 8.6
13458 34 1 32.7 50 50 50 46 126 51 60 60 47 128
1 Minimum Circuit Ampacity.
2 Dual Element, Time Delay Type.
3 HACR type per NEC.
4 Non-fused Disconnect. Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field
installed electric heat kits may exceed the factory installed disconnect amperage rating.
INSTALLATION MANUAL ZY SERIES 3-10ton 60 Hertz R-410A60
Johnson Controls Ducted Systems

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls ZY Series and is the answer not in the manual?

Johnson Controls ZY Series Specifications

General IconGeneral
BrandJohnson Controls
ModelZY Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals