Table 55: Additional Static Resistance - ZY04-12
Electric Heat kW
2
Model
Size
(Tons)
CFM
1
Cooling Only
1 2, 3
Economizer
2
,
3
4 in. Filters
2
6/6.5 9.2/10.5/11 13.8/14/16 16/16.5/17 23 24.8/25.5/27.8 32/33/34 41.7/42.4
900 0.04 0.15 --- 0.00 0.00 0.01 --- 0.01 --- --- ---
1000 0.05 0.18 --- 0.00 0.00 0.02 --- 0.02 --- --- ---
1100 0.06 0.21 --- 0.01 0.01 0.02 --- 0.03 --- --- ---
1200 0.07 0.24 --- 0.01 0.01 0.02 --- 0.03 --- --- ---
1300 0.10 0.28 --- 0.01 0.01 0.03 --- 0.03 --- --- ---
1400 0.12 0.33 --- 0.02 0.02 0.03 --- 0.04 --- --- ---
04
(3.0)
1500 0.14 0.44 --- 0.02 0.02 0.04 --- 0.04 --- --- ---
1200 0.06 0.24 --- 0.01 0.01 0.02 --- 0.03 --- --- ---
1300 0.06 0.28 --- 0.01 0.01 0.03 --- 0.03 --- --- ---
1400 0.06 0.33 --- 0.02 0.02 0.03 --- 0.04 --- --- ---
1500 0.07 0.44 --- 0.02 0.02 0.04 --- 0.04 --- --- ---
1600 0.08 0.52 --- 0.02 0.02 0.04 --- 0.05 --- --- ---
1700 0.11 0.59 --- 0.03 0.03 0.05 --- 0.05 --- --- ---
1800 0.13 0.66 --- 0.03 0.03 0.05 --- 0.06 --- --- ---
1900 0.16 0.74 --- 0.04 0.04 0.06 --- 0.07 --- --- ---
05
(4.0)
2000 0.20 0.81 --- 0.04 0.04 0.07 --- 0.08 --- --- ---
1800 0.23 0.66 --- 0.03 0.03 0.05 --- 0.06 --- --- ---
2000 0.28 0.81 --- 0.04 0.04 0.07 --- 0.08 --- --- ---
2200 0.32 0.95 --- 0.06 0.06 0.08 --- 0.09 --- --- ---
2400 0.37 1.10 --- 0.07 0.07 0.10 --- 0.11 --- --- ---
06
(5.0)
2500 0.50 1.17 --- 0.08 0.08 0.11 --- 0.12 --- --- ---
1800 0.23 0.13 --- 0.03 --- --- 0.05 --- 0.06 --- ---
2000 0.28 0.15 --- 0.04 --- --- 0.06 --- 0.07 --- ---
2200 0.32 0.18 --- 0.06 --- --- 0.07 --- 0.09 --- ---
2400 0.37 0.21 --- 0.07 --- --- 0.08 --- 0.1 --- ---
2600 0.38 0.24 --- 0.08 --- --- 0.09 --- 0.11 --- ---
2800 0.41 0.29 --- 0.09 --- --- 0.10 --- 0.12 --- ---
07
(6.0)
3000 0.45 0.35 --- 0.11 --- --- 0.12 --- 0.14 --- ---
1800 0.23 0.13 --- 0.03 --- --- 0.05 --- 0.06 --- ---
2000 0.28 0.15 --- 0.04 --- --- 0.06 --- 0.07 --- ---
2200 0.32 0.18 --- 0.06 --- --- 0.07 --- 0.09 --- ---
2400 0.37 0.21 --- 0.07 --- --- 0.08 --- 0.1 --- ---
2600 0.38 0.24 --- 0.08 --- --- 0.09 --- 0.11 --- ---
2800 0.41 0.29 --- 0.09 --- --- 0.10 --- 0.12 --- ---
A7
(6.0)
3000 0.45 0.35 --- 0.11 --- --- 0.12 --- 0.14 --- ---
2200 0.04 0.18 --- --- --- --- 0.07 --- 0.09 0.10 0.12
2600 0.06 0.24 --- --- --- --- 0.09 --- 0.11 0.12 0.15
3000 0.10 0.35 --- --- --- --- 0.12 --- 0.14 0.15 0.19
3400 0.13 0.47 --- --- --- --- 0.15 --- 0.18 0.19 0.23
3800 0.16 0.59 --- --- --- --- 0.19 --- 0.22 0.23 0.27
4000 0.17 0.66 --- --- --- --- 0.21 --- 0.24 0.25 0.30
4400 0.20 0.79 --- --- --- --- 0.25 --- 0.29 0.30 0.35
4800 0.22 0.91 --- --- --- --- 0.30 --- 0.34 0.35 0.41
5200 0.24 1.04 --- --- --- --- 0.35 --- 0.39 0.41 0.47
5600 0.26 1.17 --- --- --- --- 0.41 --- 0.45 0.47 0.54
ZY
08
(7.5),
09
(8.5),
12
(10.0)
6000 0.28 1.30 --- --- --- --- 0.48 --- 0.52 0.54 0.60
1 Add these values to the available static resistance in the respective Blower Performance Tables.
2 Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.
3 The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return
air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
INSTALLATION MANUAL ZY SERIES 3-10ton 60 Hertz R-410A 99