4 Supplement
Interface
7-segment displays
Approvals/approval marks
Site altitude up to 2000 m above sea level
Operating position any
Protection type as per DIN EN 60529, at the front IP 65, at the rear IP 20
Weight (fully equipped) LC100: approx. 150 g; LC200: approx. 200 g;
LC300: approx. 300 g
Interface type RS485
Protocol Modbus RTU
Baud rate 9600, 19200
Data format 8 data bits, no parity bit, 1 stop bit
Device address 0 to 254
No. of subscribers max. 32
Digit height
LC100, LC200 upper display: 10 mm; lower display: 7 mm
LC300 upper display: 20 mm; lower display: 13 mm
Color upper display: red; lower display: green
Places 4 (including decimal places)
Decimal places 0, 1, 2 (configurable)
Display range -1999 to 9999
Approval marks Inspection
authority
Certificate / Ins-
pection number
Inspection/test
basis
valid for
c UL us Underwriters
Laboratories
applied for UL 61010-1,
CAN/CSA C22.2
No. 61010-1
all versions