Table 69: Rack Requirements and Specicaons
(Connued)
Rack Requirement Guidelines
Rack connecon to
building structure
Secure the rack as follows:
• Secure the rack to the building structure.
• If your geographical area is earthquake-prone, secure the rack to the oor.
• Secure the rack to the ceiling brackets as well as wall or oor brackets for maximum
stability.
SEE ALSO
Rack-Mounng and Cabinet-Mounng Warnings
Cabinet Requirements
You can mount the device in a cabinet that contains a 19-in. rack.
Cabinet requirements consist of:
• Cabinet size.
• Clearance requirements.
• Cabinet airow requirements.
Table 70 on page 122 provides the cabinet requirements and specicaons.
Table 70: Cabinet Requirements and
Specicaons
Cabinet Requirement Guidelines
Cabinet size
• The minimum cabinet size is 36 in. (91.4 cm) deep. Large cabinets
improve airow and reduce chances of overheang.
122