Juniper EX4400 - DC Power Electrical Safety Guidelines for EX4400 Switches

Juniper EX4400
288 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Power Cable Warning (Japanese)
WARNING: The aached power cable is only for this product. Do not use the cable for another product.
DC Power Electrical Safety Guidelines for EX4400
Switches
For permanently connected equipment, a readily accessible disconnect device shall be incorporated
external to the equipment.
For pluggable equipment, the socket-outlet shall be installed near the equipment and shall be easily
accessible.
Be sure to connect the ground wire or conduit to a solid central oce earth ground.
A closed loop ring is recommended for terminang the ground conductor at the ground stud.
Run two wires from the circuit breaker box to a source of 48 VDC.
Ensure that the polarity of the DC input wiring is correct. Under certain condions, connecons with
reversed polarity might trip the primary circuit breaker or damage the equipment.
Provide a 20 A 2-pole breaker or a circuit breaker as per local electrical code.
NOTE: Primary overcurrent protecon is provided by the building circuit breaker. This breaker
must protect against excess currents, short circuits, and earth grounding faults in accordance
with NEC ANSI/NFPA 70.