To know the part numbers for ordering the separately orderable mounng kits, see the EX4400
Switches Datasheet.
NOTE: One person must be available to li the switch while another person secures the switch
to the rack.
CAUTION: If you are mounng mulple units on a rack, mount the heaviest unit at the
boom of the rack, and then mount the other units from the boom of the rack to the
top in decreasing order of the weight of the units.
To mount an EX4400 switch on two posts of a rack:
1. Place the switch on a at, stable surface.
2. Wrap and fasten one end of the ESD wrist strap around your bare wrist, and connect the other end
of the strap to a site ESD point.
3. Aach the two-post mounng brackets (provided with the switch) to the side panels of the switch
chassis by using the screws to aach the brackets (provided with the switch).
To mount the switch ush with the posts:
a. Align the L-shaped (front) end of the mounng brackets ush with the front panel of the switch
chassis.
b. Insert the screws into the aligned holes on the chassis (see No Link Title). Tighten the screws.
Figure 84: Aach the Two-Post Mounng Brackets Flush with the Front Panel of the Switch
To mount the switch along the middle of its side panels:
a. Align the L-shaped (front) end of the mounng brackets along the middle of the side panels.
b. Insert the screws into the aligned holes on the chassis (see No Link Title). Tighten the screws.