Table 32: Line Card Power Consumption (continued)
MX10K-LC2101 (400 Gigabit
Ethernet mode @104° F (40°
C))
MX10K-LC2101 (240 Gigabit
Ethernet mode @104° F (40°
C))Number of Line Cards
5700 W4700 W4
7125 W5875 W5
8550 W7050 W6
9975 W8225 W7
11400 W9400 W8
For example, for an MX10008 with eight MX10K-LC2101 line cards, the maximum power consumption
@400 Gigabit Ethernet mode is:
= 8* 1425 W= 11400 W
3. Add the power consumption from Step 1 and the total line card consumption from Step 2.
To continue from the previous example, add the wattage from eight cards to a redundant configuration.
(11400 W) + (2650 W)
= 14050 W required
Calculating the Number of Power Supplies Required for Your MX10008 Configuration
Use this procedure to calculate the number of power supplies required by your router configuration. The
minimum power configuration for MX10008 routers is three power supplies.
To calculate the number of power supplies required for your minimum router configuration:
1. Determine the power available from the power supplies. Table 33 on page 102 shows the power available
for installed power supplies.
Table 33: Total Power Available
With Five Power
Supplies
With Four
Power Supplies
With Three
Power SuppliesPower Supply Module Models
13,500 W10,800 W8100 WJNP10K-PWR-AC