EasyManua.ls Logo

Kampmann Katherm HK - Page 75

Kampmann Katherm HK
84 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Katherm HK
Assembly, installation and operating instructions
75
Parameter Function Standard Min. Max. Unit Katherm HK
9
Katherm HK
E
10
P030 Ventilation temperature activation 12 0 255 °C 12 12
P031 Ventilation interval 27 0 255 °C 27 27
P032 Rinsing function: maximum idle time of fan 15 0 255 min 15 15
P033 Rinsing function: duration of the rinsing function 120 0 255 s 120 120
P034 Rinsing function: activation in operating modes 0 0 3 - 0 0
P035
Fan run-on time after an operating mode is switched
to stage 1
0 0 255 s 0 0
P036 Type of setpoint setting 0 0 1 - 0 0
P037 Display 1 0 7 - 1 1
P038 Lock/disable function on the control unit 72 0 255 - 72 74
P039 Function of digital output V2 (in a 2-pipe system) 0 0 3 - 0 0
P040 Valve actuation by pulse width modulation 0 0 1 - 0 0
P041
Reset time of PI controller to activate the fan in
automatic fan mode
0 0 20 min 0 0
P042 Fan setting: lock and activate fan stages 0 0 127 - 0
P043 Function of digital input DI1 0 0 22 - 5
P044 Function of digital input DI2 0 0 22 - 0
P045
Threshold voltage for potentiometer to switch on
the unit
10 0 100 kOhm 10 10
P046
Temperature setting corresponds to the minimum
resistance value = 10 kOhm in the potentiometer
18 12 34 °C 18 18
P047
Temperature setting corresponds to the maximum
resistance value = 100 kOhm in the potentiometer
24 13 35 °C 24 24
P048
Threshold voltage for potentiometer for starting up
the fans
10 0 100 kOhm 10 10
P049
Threshold voltage for potentiometer for maximum
fan speed
90 0 100 kOhm 90 90
P050 Fan setting: max. fan speed 100 0 100 % 100 100
P051 Fan setting: min. fan speed 0 0 90 % 15 15
P052 Fan setting: activation of fan speed limit 0 0 1 - 1 1
P053
Valve activation by pulse width modulation of valve
switching cycle
15 10 30 min 15 12
P054 Configuration of bus system 0 0 2 - 0 0
P055
Display of heating/cooling symbols in automatic
mode
0 0 1 - 1 0
P056 DI2 setting (polarity) when DIP 4 = ON 1 0 1 - 1 1
P057
Reset setpoint to the value of P01 (after changing an
operating program)
0 0 1 - 0 0
P058 Sensor calibration: sensor AI1 0 -99 127 K/10 0 0
P059 Supply air temperature setpoint in heating mode 35 0 50 °C 35 35
P060 Supply air temperature setpoint in cooling mode 18 0 50 °C 18 18
P061 Sensor calibration: sensor in the KaController 0 -99 127 K/10 0 0
P062 Sensor calibration: sensor AI2 0 -99 127 K/10 0 0
P063 Outside temperature <P63 fan increase by P122 0 -99 127 °C 0 0
P064 Sensor calibration: sensor AI3 0 -99 127 K/10 0 0
P065 reserved - - - - - -
P066 Master/Slave assignment in CANbus 0 0 1 - 0 0
P067 Serial CAN bus address 1 1 125 - 1 1
P068 Logic of the hydronic algorithms 0 0 7 - 0 0

Table of Contents

Other manuals for Kampmann Katherm HK

Related product manuals