Venkon
Assembly, installation and operating instructions
7
2.2 Limits of operation and use
Limits of operation
Min./max. water temperature °C/°F 40-90 / 104-194
Min./max. air intake temperature °C/°F 6-40 / 43-104
Min./max. air humidity % 15-75
Min. operating pressure bar/kPa -
Max. operating pressure bar/kPa/psi 10/1000/145
Min./max. glycol percentage % 25-50
Tab.1: Limits of operation
Operating voltage 115 V/ 60 Hz
Power/Current consumption On the type plate
Tab.2: Operating voltage
We would refer to VDI-2035 Sheets 1 & 2, DIN EN 14336 and DIN EN 14868 with regard to the properties of the medium
used to protect the equipment. The following values provide further guidance.
The water used should be free of contamination, such as suspended substances and reactive substances.
Water quality
pH value (at 20 °C / 68°F) 8-9
Conductivity (at 20 °C / 68°F)) μS/cm / ppm <700 / <350
Oxygen content (O
2
) mg/l / (lb/gal) <0.1 / (<0.00000083)
Hardness °dH / ppm CaCO
3
4-8.5 / 0.224-0.476
Sulphur ions nicht messbar
Sodium ions (Na
+
) mg/l / (lb/gal) <100 / (<0.00083)
Iron ions (Fe
2+
) mg/l / (lb/gal) <0.1 / (<0.00000083)
Manganese ions (Mn
2+
) mg/l / (lb/gal) <0.05 / (<0.000000415)
Ammonia ions (NH
4+
) mg/l / (lb/gal) <0.1 / (<0.00000083)
Chlorine ions (CI) mg/l / (lb/gal) <100 / (<0.00083)
CO
2
<50
Sulfate ions (SO
4
2-
) mg/l / (lb/gal) <50 / (<0.000415)
Nitrite ions (NO
2-
) mg/l / (lb/gal) <50 / (<0.000415)
Nitrate ions (NO
3-
) mg/l / (lb/gal) <50 / (<0.000415)
Tab.3: Water quality