EasyManua.ls Logo

Kamstrup MULTICAL 803 - Flow sensor positioning guidelines

Kamstrup MULTICAL 803
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9Kamstrup A/S • 55122412_A1_GB_2019-03
MULTICAL® 803 & ULTRAFLOW®
3.4 Flow sensor position
Kamstrup flow sensors require neither straight inlet nor straight outlet to meet the Measuring
Instruments Directive (MID) 2014/32/EU, OIML R75:2002 and EN 1434:2015. A straight inlet section
will only be necessary in case of heavy flow disturbances before the meter. It is recommended to
follow the guidelines of CEN CR 13582.
A Recommended position.
B Recommended position.
C Unacceptable position due to risk of air
build-up.
D Acceptable position in closed systems.
E Ought not to be placed immediately after
a valve, with the exception of block valves
(ball valve type) which must be fully open
when not used for blocking.
F Ought not to be placed immediately before
or after a pump.
G Ought not to be placed immediately after a
double bend in two planes.
A
B
C
D
E
F
G
In order to avoid cavitation, the back pressure at the flow sensor (the pressure at the flow sensor
outlet) must be minimum 1.5 bar at q
p
(nominal flow) and minimum 2.5 bar at q
s
(maximum flow).
This applies to temperatures up to approx. 80 °C. The flow sensor must not be exposed to pressure
lower than the ambient pressure (vacuum).

Other manuals for Kamstrup MULTICAL 803

Related product manuals