Installation and user’s guide
MULTICAL® 603
θ: 2 °C ...180 °C
: 3 K ...178 K
Cooling meter (E3)
θ: 2 °C ...180 °C
Heat meter (E1)
: 3 K ...178 K
∆Θ∆Θ
S/N: 80000095/K8/17
DK-0200-MI004-040
qp, p/l: See display
TS 27.02 012
θhc: See display
Pt500-EN60751
Type: 603C219
Battery, 1 x D-cell
θ: 2 °C ...180 °C
: 3 K ...178 K
Cooling meter (E3)
θ: 2 °C ...180 °C
Heat meter (E1)
: 3 K ...178 K
∆Θ∆Θ
S/N: 80000095/K8/17
DK-0200-MI004-040
qp, p/l: See display
TS 27.02 012
θhc: See display
Pt500-EN60751
Type: 603C219
Battery, 1 x D-cell

Other manuals for Kamstrup MULTICAL 603

Questions and Answers

  • R
    Robin BennettJul 27, 2025
    How to fix Kamstrup Measuring Instruments with no display function?
    • B
      bgreenJul 27, 2025
      If your Kamstrup Measuring Instruments display is empty, the issue is likely a missing power supply. Try changing the battery or checking the mains supply to ensure it provides 3.6 VDC.
  • A
    ashley10Jul 31, 2025
    Why is my Kamstrup MULTICAL 603 not accumulating energy and volume?
    • T
      Timothy HarringtonJul 31, 2025
      If your Kamstrup Measuring Instruments aren't accumulating energy (e.g., MWh) and volume (m3), there could be several reasons: * Check the error code displayed in the "INFO" section. * If “INFO” = 00000000, ensure the flow direction matches the arrow on the flow sensor. * If “INFO” = xXxxxxxx, xxXxxxxx or xXXxxxxx, check the temperature sensors and replace the sensor pair if defective.
  • C
    Chase DeleonAug 4, 2025
    What to do if my Kamstrup Measuring Instruments shows incorrect volume accumulation?
    • A
      Albert JacksonAug 4, 2025
      If your Kamstrup Measuring Instruments shows incorrect volume accumulation, the pulse figure configuration might be faulty. Verify that the pulse figure on the flow sensor matches the calculator's configuration.
  • C
    christopher47Aug 9, 2025
    Why does my Kamstrup MULTICAL 603 Measuring Instruments accumulate volume but not energy?
    • C
      Caleb KingAug 9, 2025
      If your Kamstrup Measuring Instruments accumulates volume (m3) but not energy (e.g. MWh), consider these potential causes: * If “INFO” = x99xxxxx, it indicates an invalid temperature difference (t1?t2). * The inlet and outlet sensors may have been interchanged during installation or connection; ensure they are mounted correctly. * The heat/cooling cut-off may be configured to a value that is too low. Reconfigure it to a suitable value, or disconnect the cut-off function by setting it to 250 °C.
  • C
    Cindy ChristensenAug 13, 2025
    Why is the temperature reading incorrect on my Kamstrup MULTICAL 603?
    • J
      Jasmine EvansAug 13, 2025
      An incorrect temperature reading on your Kamstrup Measuring Instruments could be due to a defective temperature sensor or insufficient installation. Replace the sensor pair and check the installation.
  • W
    Wanda LopezAug 17, 2025
    Why is the temperature or energy accumulation slightly low on my Kamstrup MULTICAL 603 Measuring Instruments?
    • D
      Deborah JarvisAug 17, 2025
      If the temperature indication or energy accumulation is slightly low on your Kamstrup Measuring Instruments, it may be due to bad thermal sensor contact, heat dissipation, or sensor pockets that are too short. Ensure the sensors are pushed to the bottom of the sensor pockets, insulate the sensor pockets, or replace them with longer pockets.
  • M
    Michelle BlakeAug 21, 2025
    How to troubleshoot Kamstrup Measuring Instruments when the optical interface doesn't respond?
    • K
      Katherine FrazierAug 21, 2025
      If the optical interface on your Kamstrup Measuring Instruments does not respond, the optical interface may be disabled or the optical readout head is positioned incorrectly. Turn the optical readout head so that the cable turns upwards.

Summary

General Information

Mounting of temperature sensors

Short direct sensor (DS)

Instructions for mounting short direct temperature sensors (DS) up to DN25.

Pocket sensor (PL)

Instructions for mounting pocket temperature sensors (PL) in welding sleeves or Y-pieces.

Mounting of flow sensor

Mounting of couplings and short direct sensor in flow sensor

Details on mounting couplings and short direct sensors in flow sensors.

Mounting of ULTRAFLOW ≤ DN125

Guidance on installing ULTRAFLOW® sensors for sizes up to DN125.

Mounting of ULTRAFLOW 54 ≥ DN150

Reference to installation guide for ULTRAFLOW® sensors 54 and above DN150.

Flow sensor position

Recommended and unacceptable positions for flow sensor installation.

Mounting the calculator

Compact mounting

Procedure for mounting the MULTICAL® calculator directly onto the ULTRAFLOW®.

Wall-mounting

Instructions for wall-mounting the MULTICAL® calculator using a wall fitting.

Electrical connection

Connection of power supply

Details on battery supply and mains supply options for the MULTICAL®.

Testing of function

Set-up via front keys

Kamstrup MULTICAL 603 Specifications

General IconGeneral
Flow SensorUltrasonic
Battery LifeUp to 16 years
Power SupplyBattery
Communication OptionsM-Bus, Wireless M-Bus, Modbus, BACnet
DisplayLCD
ApplicationHeating and Cooling
Pressure RatingPN16
ApprovalMID
AccuracyClass 2