EasyManua.ls Logo

Kane KANE900 Plus - 10. PROBLEM SOLVING

Kane KANE900 Plus
38 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
KANE900 Plus Operators Manual Page 28
12. PRODUCT SPECIFICATION
Parameter Resolution Accuracy Range
Temp Measurement
Flue Temperature
Inlet Temperature
1.0°C/F
0.1°C/F
+
2.0°C +0.3% reading
+
1°C +0.3% reading
0-600°C/32-1112°F
0-50°C/32-122°F
Gas Measurement
Oxygen
Carbon Monoxide
Carbon Monoxide, H
2
compensated
Nitric Oxide
(optional)
Nitrogen Dioxide
(optional)
Pressure (optional)
Carbon Dioxide
*2
Losses
*2
Efficiency
*2
Excess Air
*2
Temp (Nett)
*2
CO/CO
2
ratio
*2
Poison Index
*2
0.1%
1ppm,mg/m
3
1ppm,mg/m
3
1ppm,mg/m
3
1ppm,mg/m
3
0.1mbar
0.1%
0.1%
0.1%
0.1%
1.0°C/F
0.0001
0.01%
+
0.2%
*1
+
20ppm <400ppm
*1
+
5% >400ppm
+
20ppm <400ppm
*1
+
5% <5000ppm
+
10% >5000ppm
+
5ppm <100ppm
*1
+
5% >100ppm
+
5% full scale
+
5.0% full scale
+
0.3% reading
+
1.0% reading
+
1.0% reading
+
0.2%
+
2°C +0.3% reading
+
0.0001
+
0.01
0-21%
0-4000ppm, 0-5000mg/m
3
0-10,000ppm, 0-12,000mg/m
3
0-5000ppm, 0-6700mg/m
3
100ppm, 200mg/m
3
150 mbar
0-99.9%
0-99.9%
0-99.9%
0-2885.0%
0-600°C/32-1112°F
0-0.9999
0-99.99
Pre-programmed Fuels
Natural gas, Town gas, Gascor, Light Oil, Heavy Oil,
Propane, Butane, Anthracite, Coke, Coal, Kinsale Gas.
Dimensions
Weight
Handset
Probe
1kg
220mm x 55mm x 120mm
L240mm x Dia8mm with 285mm long stainless steel shaft,
type K thermocouple and 1.5m long neoprene hose
Ambient Operating Range
+0°C to +40°C/10% to 90% RH non condensing
Power Supply (battery charger)
Input: 110Vac/220 Vac nominal
Output: 12 Vac off load
Battery Life
>8 hours from full charge
*1
Using dry gases at STP
*2
Calculated
Keison Products www.keison.co.uk sales@keison.co.uk Tel: 01245 600560 Fax: 01245 600030