Address Words Description Value Format
0xD020 2 Byte sequence for oat on the Modbus
(1=as dened // 0=reversed)
0-1 unsigned
long
0xD022 2 Frequency correction (0=Auto // 1=50
Hz // 2=60 Hz)
0-2 unsigned
long
0xD024 2 Stage monitoring (0=No, 1=Yes) 0/1 unsigned
long
0xD026 2 Temperature measurement (1=Yes //
0=No)
0/1 unsigned
long
0xD028 2 Fan relay
(1=available // 0=not available)
0/1 unsigned
long
0xD02a 2 Temperature [0.1 °C] that triggers the
fan when the threshold is exceeded
0-700 unsigned
long
0xD02c 2 Temperature [0.1 °C] that causes the fan
to switch o when the value falls below
the threshold
0-700 unsigned
long
0xD02e 2 Temperature [0.1 °C] that triggers the
stages when the value falls below the
threshold
0-700 unsigned
long
0xD030 2 Temperature [0.1 °C] that causes the
stages to switch o when the threshold
is exceeded
0-700
unsigned
long
0xD032 2
0xD034 2
0xD036 2
0xD038 2
0xD03A 2
0xD03C 2
0xD03E 2
Switching performance
0xD042 2 Percentage of smallest available stage
before activation
70-150 unsigned
long
0xD044 2 Percentage of smallest available stage
before stages can be switched o
70-150 unsigned
long
0xD046 2 Time before message "Compensation
unit too small" is displayed [s]
3-3000 unsigned
long
0xD048 2 Idle time after compensation [s] 0-300 unsigned
long
0xD04A 2 unsigned
long
0xD04C 2 Switching interval [s] 0-10 unsigned
long
Data point description for the Modbus protocol