Control and display panel
4 Setting Range of the Congurable Parameters:
Stage state:
Stage switching mode Automatic, Manual o, Manual on
Commissioning:
Password 4 digits, numerical, no password = 9999
(meaning all functions are accessible)
Primary current 1 A to 999999 A
Secondary current 1 and 5 A
Consumption target cosφ ind. 0.80 to cap. 0.80
Recovery target cosφ ind. 1.0 (cannot be changed)
Primary voltage 1 V to 99999 V Ph-Ph
Secondary voltage 1 V to 999 V Ph-Ph
Rot. eld U L1N, L2N, L3N, L12, L23, L31
Rot. eld I L1, L2, L3, -L1, -L2, -L3
Stage power learning mode Yes, No
Stage power 0 to 999.9 kvar
Discharge time 0 to 999 sec.
Switching performance:
Hysteresis connection 70 to 150 %
Hysteresis switch-o 70 to 150 %
Switching performance Priority Operation cycles, runtime
Alarm relay time 3 to 3000 sec.
Idle time 0 to 300 sec.
Switching interval 0 to 10 sec.
FTS alarm cosφ ind. 0.70 to 1.0
Attenuation coecient Qmiss 0 to 9
Attenuation coecient voltage 0 to 9
Attenuation coecient current 0 to 9