EasyManua.ls Logo

KEB COMBIVERT G6 - CP38 Inverter Address; CP39 Last Error; CP40 Parameter Set Copy Function

KEB COMBIVERT G6
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
23
CP-Parameter for open-loop operation
CP37 Display Response Restart
0
1)
Immediate disabling of modulation
Remove fault; reset
1*
2)
Quick stopping / disabling of modulation after reach-
ing speed 0
2*
2)
Quick stopping / holding torque at speed 0
3
2)
Immediate disabling of modulation
Autoreset, if no fault
is present
4*
2)
Quick stopping / disabling of modulation after reach-
ing speed 0
5*
2)
Quick stopping / holding torque at speed 0
6* non Motor temperature is not monitored. The drive does
not execute an automatic abnormal stopping during
the pre-warning period. The pre-warning message
can only be issued via a digital output (switching con-
dition 9: „dOH warning“). After expiration of the pre-
warning period, the inverter changes to „9: ERROR
drive overheat“.
inapplicable
7 non Motor temperature is not monitored. Error „9: Error!
drive overheat“ is never triggered. No message via
digital output possible.
8
2)
Malfunction is only triggered when the inverter modu-
lates.
Remove fault; reset
9 As value 6, additionally the motor monitoring is also
active when the modulation is switched off.
1)
ERROR ! drive overheat
2)
ABN.STOP drive overheat
*) If the drive is still hot after 10 seconds, „ERROR drive overheat" is triggered and the modu-
lation is switched off!
CP38 Inverter address
Co-domain Setting Description
0…239 1 Setting of the bus address, whereby the inverter can be ad-
dressed by "COMBIVIS" or another control. If several inverters
are operated simultaneously at the bus, it is absolutely neces-
sary to assign different bus addresses to them, since otherwise
it leads to communication failures.
CP39 last error
Co-domain Setting Description
0…255 1 The inverter stores the eight errors that occurred last. Displays
the error that occurs last.
CP40 parameter set copy function
Co-domain Setting Description
-4…7 1 CP40 denes the source parameter set. By default set 0 is ad-
justed as target set in the CP mode.
0…7 All programmable parameters of the source set are copied into the tar-
get set.
further on next side

Other manuals for KEB COMBIVERT G6

Related product manuals