23
CP-Parameter for open-loop operation
CP37 Display Response Restart
0
1)
Immediate disabling of modulation
Remove fault; reset
1*
2)
Quick stopping / disabling of modulation after reach-
ing speed 0
2*
2)
Quick stopping / holding torque at speed 0
3
2)
Immediate disabling of modulation
Autoreset, if no fault
is present
4*
2)
Quick stopping / disabling of modulation after reach-
ing speed 0
5*
2)
Quick stopping / holding torque at speed 0
6* non Motor temperature is not monitored. The drive does
not execute an automatic abnormal stopping during
the pre-warning period. The pre-warning message
can only be issued via a digital output (switching con-
dition 9: „dOH warning“). After expiration of the pre-
warning period, the inverter changes to „9: ERROR
drive overheat“.
inapplicable
7 non Motor temperature is not monitored. Error „9: Error!
drive overheat“ is never triggered. No message via
digital output possible.
8
2)
Malfunction is only triggered when the inverter modu-
lates.
Remove fault; reset
9 As value 6, additionally the motor monitoring is also
active when the modulation is switched off.
1)
ERROR ! drive overheat
2)
ABN.STOP drive overheat
*) If the drive is still hot after 10 seconds, „ERROR drive overheat" is triggered and the modu-
lation is switched off!
CP38 Inverter address
Co-domain Setting Description
0…239 1 Setting of the bus address, whereby the inverter can be ad-
dressed by "COMBIVIS" or another control. If several inverters
are operated simultaneously at the bus, it is absolutely neces-
sary to assign different bus addresses to them, since otherwise
it leads to communication failures.
CP39 last error
Co-domain Setting Description
0…255 1 The inverter stores the eight errors that occurred last. Displays
the error that occurs last.
CP40 parameter set copy function
Co-domain Setting Description
-4…7 1 CP40 denes the source parameter set. By default set 0 is ad-
justed as target set in the CP mode.
0…7 All programmable parameters of the source set are copied into the tar-
get set.
further on next side

Other manuals for KEB COMBIVERT G6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT G6 and is the answer not in the manual?

KEB COMBIVERT G6 Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT G6
CategoryDC Drives
LanguageEnglish

Related product manuals