20
CP-Parameter for open-loop operation
CP30 ANOUT1 function
CP30 denes the function of analog output 1. The output at the analog output is made in a
range of 0…±10 V.
Value Function Scaling factor
0…100 % (0…±100 %)
0 Absolute actual frequency (CP01) 0…100 Hz
1 Absolute set frequency (CP02) 0…100 Hz
2 Actual frequency (CP01) 0…±100 Hz
3 Set frequency (CP02) 0…±100 Hz
4 Output voltage (CP09) 0…500 V
5 DC link voltage (CP07) 0…1000 V
6 Apparent current (CP04) 0…2 • rated current
7 Active current (ru17) 0…2 • ±rated current
8…10 reserved –
11 Absolute active current (ru17) 0…2 • rated current
12 Power module temperature (ru38) 0…100 °C
13…21 reserved –
22 AN1 pre amplier display (ru27) 0…100 %
23 AN1 post amplier display (ru28) 0…400 %
24…25 reserved –
26 Active power (ru81) 0…±2 • rated power
CP32 Condition SB0
The values 0…101 correspond to those of CP33.
The switching level for transistor output 1 is preset to 4.00.
CP33 Condition SB2
The switching level for relay output 1 is adjusted with CP34 (setting: 100.00).
Value Function
0 No function (generally off)
1 Generally on
2 Run signal; also by DC-braking
3 Ready signal (no error)
4 Error
5 Error (without auto-reset)
6 Warning or error message (also at fast stop)
7 Overload pre-warning (OL) up to 80 %
8 Heat sink temperature pre-warning (OH) up to 70 °C
9 Motor temperature pre-warning (dOH) → CP37
10 Motor protection relay function pre-warning (OH2) → CP27
11 Internal temperature pre-warning
12 Cable breakage 4...20 mA on analog input 1
13 Cable breakage 4...20 mA on analog input 2
14 max. constant current (I>CP25) exceeded
15 max. ramp current (I>CP24) exceeded
16 DC-braking active
17 Power-off function active
18 Brake control
19 Speed control difference > level
20 Actual value=setpoint (CP03=Fcon; rcon; not at noP, LS, error, SSF)
21 Accelerate (CP03 = FAcc, rAcc, LAS)
22 Decelerate (CP03 = FdEc, rdEc, LdS)
23 Real direction of rotation = set direction of rotation
further on next side