P30 UDP commands
UDP Programmers Guide V2.01
35
© KEBA
Command structure
Command Parameters Additional Description
failsafe [t]
[c] [s]
[t]: Time delay
Timeout in seconds before the failsafe mode
will be activated. The device must receive a
curr, currtime or ena command to pre-
vent the activation.
Possible values: 0; 10 - 600
0: Disable failsafe mode
[c]: Current setting
Maximum charging current in failsafe mode.
Possible values: 0; 6000 - 63000
0: Disable charging in failsafe mode (similar
to ena 0)
[s]: Saved value
0: The failsafe function is active until the de-
vice is restarted.
1: The failsafe function is active and saves
the settings into the EEPROM. The failsafe
function will still be active after a reboot.
Reply structure
Field Contents Additional Description
- TCH-OK: done Generic confirmation message
3.4 UDP status messages
P30 will send status messages to the source/IP address of the last UDP
command it received. That means if there is only one application in the net-
work sending commands to the charging station, the application will get the
information about the most important state changes without the need to poll
reports. P30 will provide the information about the following state changes:
“State” (see “report 2”)
“Plug” (see “report 2”)
“Input” (see “report 2”)
“Enable sys” (see “report 2”)
“Max curr” (see “report 2”)
“E pres” (see “report 3”)