Troubleshooting
55 / 1802017/11
6 Troubleshooting
All work exceeding the activities described in Chapter may only be carried out by specialist staff (see 2.2).
• Pay attention to the notes described in 5.1 and perform these if necessary
Error Possible cause Remedial measure / Chapter
Battery fault Battery is missing, is faulty or voltage too
low
Check battery connection, if necessary
Replace battery.
Power outage Power supply has failed None, general power outage
Fuse for complete system faulty Determine the reason for the fuse
failure and replace the fuse if
necessary or switch it on
Device fuse (microfuse) failed Have the fuse checked or replaced by
specialist staff.
Mains supply cable interrupted Check mains supply cable
Level fault Illogical sequence of levels detected inform Customer Services
Alarm level exceeded Power outage Restore power supply
Wastewater pump has overheated,
winding temperature switch has triggered
Self-resetting when the motor cools
down. Replace pump if the temperature
fault persists.
Level sensor (oat switch) blocked by
deposits
Cleaning the lifting station / 5.4.2
Wastewater pump faulty inform Customer Services
Max. run time Pump is running too long per pumping
process
Ventilation not working
- Check design and if necessary inform
Customer Services
- Run-on time too long / set shorter
(potentiometer in control unit)
Clean ventilation bores (see Chap.
5.4.2 clean lifting station)
Start-up cycle limit Pump starts up too often at short
intervals
Backwater preventer faulty
Check design, if necessary inform
Customer Services
- check and replace if necessary