Chapter 6 List of Parameters
67
Function
code
Name Descriptions Unit
Factory
setting
Modif
.
Setting
range
1: Enable
Thou : Reserved
A8.01 Fault masking
selection 1
: Communication
fault masking selection
: Relay fault
masking selection
:
EEPROM fault
masking selection
place of LED: Reserved
0: Disable.Stop when fault happen
1: Disable.Continue operating when
fault happen
2: Enable
1 2000 X 0 2222H
A8.02 Fault masking
selection 2
LED: Open phase fault
masking selection for input
: Open phase fault
masking selection for output
Hundr : fault masking
selection for over limit of deviation of
speed
:
fault masking
overheat
0: Disable.Stop when fault happen
1: Disable.Continue operating when
fault happen
2: Enable
1 00 X 0 22H
A8.03
Motor overload protection
mode selection
0: Disabled
1: Common mode
(with low speed compensation)
2: Variable frequency motor
(without low speed compensation)
1 1 X 0 2
A8.04 Auto reset times 0: Nofunction
1 100: Auto reset times
Note: The IGBT protection (E010) and
external equipment fault (E015) cannot
be reset automatically.
1 0 X 0 100
A8.05 Reset interval 2.0 20.0s/time 0.1s 5.0s X 20 200
A8.06 Fault lockingfunction
selection.
0: Disable.
1: Enable.
1 0 X 0 1
Group b0.Motor 1 parameters
b0.00 Asynchronous motor 1
rated power
0.2 999.9KW 0.1 0 X 2 9999
b0.01 Asynchronous motor 1
rated voltage
0 Rated voltage 1 0 X 0 999