Operating Instruction
Healthcare chiller of the KSC Series
Version „Revision 09“
Type KSC 215-L-U/S
page 1von138
\\FILER02\Allgemein\02 - Technische Unterlagen KKT\Originale\830xxx Bedienungsanleitungen\KSC\83002302.Ka KKT chillers_KSC215-US.doc
Manufacturer
ait-deutschland GmbH T +49 9228 9977 0
Industriestraße 3 F +49 9228 9977 149
95359 Kasendorf E info@kkt-chillers.com
Germany W www.kkt-chillers.com
Representative in the US and Service Center
KKT chillers, Inc. T 847 734 1600
1280 Landmeier Road F 847 734 1601
Elk Grove Village, IL 60007 TF 866 517 6867
USA E support@kkt-chillersusa.com
YOUR LOCAL SERVICE CONTRACTOR IS:
COMPANY NAME:
PHONE NUMBER: FAX NUMBER:

Table of Contents

Other manuals for KKT KSC Series

Questions and Answers

  • D
    Daniel RileyAug 13, 2025
    Why KKT Chiller doesn't have enough refrigeration power?
    • R
      Richard StoneAug 13, 2025
      Insufficient refrigeration power in your KKT Chiller can stem from several causes: air in the water circuit, a water agitation quantity that has fallen below the minimum, inadequate fresh air supply to the condenser, or insufficient refrigerant in the circuit. To resolve this, vent the system, ensure the water pipe cross-section is correctly designed (potentially opening the check valve fully or increasing the pipe cross-section), ensure sufficient fresh air supply and removal (eliminating any short-circuit between fresh and exhaust air), and locate and seal any leaks before refilling the refrigerant circuit.
  • E
    Eric RobinsonAug 16, 2025
    What to do if KKT KSC refrigerating machine starts and stops short-termed?
    • S
      santoskristinAug 17, 2025
      If your KKT Chiller's refrigerating machine starts and stops frequently, it may be due to insufficient fresh air supply for the condenser, causing the high-pressure pressostat to protect against overload. Another cause could be low pressure in the refrigerant circuit due to refrigerant leaks, which causes the pressure switch to shut down the compressor. Ensure adequate fresh air supply and eliminate any short-circuits between fresh air and exhaust air. Also, find and seal any refrigerant leaks before refilling the circuit.
  • D
    David BushAug 20, 2025
    What causes still malfunction of refrigerating machine KKT?
    • H
      hrobinsonAug 20, 2025
      A persistent malfunction in your KKT refrigerating machine could be due to low pressure in the refrigerant circuit, possibly from a refrigerant leak, a dirty dryer in the liquid pipe, a defective pressure relief valve, or issues with the expansion valve. High pressure in the refrigerant circuit, caused by a dirty condenser, a defective fan, high outside temperature, a faulty pressure sensor for condenser control, or a defective frequency inverter, can also be the reason. Locate and seal any leaks, then refill the circuit. Replace the dryer, pressure relief valve, or expansion valve as needed. Clean the condenser, correct any electrical issues, check the fuses, spray the condenser with water, and replace the pressostat or frequency inverter if necessary.
  • D
    daniel43Aug 25, 2025
    What to do if there is a malfunction of plant/system KKT Chiller?
    • E
      Elizabeth WrightAug 26, 2025
      A malfunction in the KKT Chiller plant/system could stem from several causes: power failure asymmetry, over or low voltage, a defective temperature sensor, malfunctions in the Simatic modules, or the chiller simply indicating a 'not ok' status. Check the mains connection and asymmetry relay, inspect the sensor clamp and measure resistance, check the MMC-Card, the 24VDC power supply and fuses, check the fuse, data transfer cable, and overvoltage protection.
  • A
    Angela PatrickAug 28, 2025
    Why do compressors 18M1 and 21M1 stop in KKT Chiller?
    • R
      Richard RichardsonAug 28, 2025
      The compressors 18M1 and 21M1 in your KKT Chiller might stop because the Klixon/INT69 has tripped or is defective. Check the fuses. Allow the compressor to cool down, and consider cleaning the condenser or improving fresh air supply. If necessary, replace the Klixon/INT69.
  • H
    heatherjonesSep 1, 2025
    What causes malfunction of pump 17M1 in KKT KSC Chiller?
    • L
      Lori MaloneSep 1, 2025
      A malfunction of pump 17M1 in your KKT Chiller may occur due to several reasons: the main switch not being switched on, a defective motor protector, a blown fuse for the control current, a defective pump motor, the flow switch responding, or a shortage of water. Switch on the main switch. Replace the motor protector. Replace the fuse. Replace the complete pump. Check the water flow and system pressure, and clean the strainer.
  • B
    Betty LongSep 5, 2025
    Why KKT KSC pump makes gurgling noise?
    • A
      Alexis RamirezSep 5, 2025
      If the KKT Chiller pump is making a gurgling noise, it is likely that the circuit is not completely vented. Vent the system and fill it up with water/Ethylene glycol.
  • S
    Sara DuncanSep 8, 2025
    What to do if KKT KSC has leaking slide seal?
    • C
      Carol HarrisSep 8, 2025
      If there is a puddle at the bottom of the KKT Chiller pump due to a leaking slide seal, it could be caused by air on top of the pump or dirt in the water circuit. Check the air vent on top of the pump and change the pump if necessary. Flush and clean the water circuit, then refill it with a new 35-38vol% water ethylene glycol mixture.

Summary

General Remarks and Safety Warnings

Safety Warnings

Crucial safety precautions, PPE requirements, and operating restrictions for safe use.

General Description

Functional Description

Explanation of the chiller's operational principles, components, and control systems.

Brief Operating Instructions

Installation, Maintenance, and Repair

Guidance for qualified personnel on servicing, maintaining, and repairing the chiller.

Filling with Water-Ethylene Glycol Mixture

Procedure for correctly filling the cooling circuit with the specified water-glycol mixture.

Setting the Clock in the SPS

Step-by-step guide to setting the date and time on the operator panel.

Technical Specifications

Data Sheet

Detailed technical data including dimensions, capacity, refrigerant, and electrical parameters.

Installing the Chiller

Troubleshooting

Typical Failures

Table listing common problems, their causes, and recommended solutions for quick diagnosis.

Automatic Restart Explanations

Details on chiller behavior and recovery after power interruptions or main switch cycles.

Description of Individual Parts

Compressor

Information on the Copeland Scroll compressor, including safety, general instructions, and technical data.

Frequency Inverter

Information on the YASKAWA E7-Series frequency inverter used for condenser fan speed control.

Primary Water Pump

Details on the Grundfos CR10-5 pump and its associated 3.0kW VEM motor.

Safety Notes

Notes for Refrigerant

Safety data for refrigerants (R134a, R407C, R404A), potential dangers, and first-aid measures.

KKT KSC Series Specifications

General IconGeneral
BrandKKT
ModelKSC Series
CategoryChiller
LanguageEnglish