TP-6376 3/0822 Section 1 Specifications and Features
1.6.6 Air Cleaner Restriction Gauge
The air cleaner restriction gauge mounted on the air
cleaner helps determine the air cleaner change interval.
The air cleaner restriction gauge monitors air flow
through the air cleaner. Decreased air flow indicates a
clogged air filter element. The air cleaner restriction
gauge continuously displays restriction readings
indicated as vacuum (see Figure 1-23).
273113
10
15
19
22
25
1
2
3
1. Push down to reset 2. Display 3. Gauge window
Figure 1-23 Air Cleaner Restriction Gauge
When the gauge reaches the maximum allowable
restriction, the gauge window turns red, indicating air
filter element needs replacement. To reset the gauge,
push the gauge top down and release.
1.6.7 Spare Tire, 60--200KRP
Towable units are available with a lockable spare tire,
hydraulic jack, and wheel lug nut wrench.
1.6.8 Utility Box
A lockable utility box is available for storing the load lug
wrench, hydraulic jack, and wheel lug nut wrench.
1.6.9 Voltage Selector Switch
Some generator sets include a selector switch providing
the ability to change between low wye and high wye
voltages. The 60--200KRP models also have a single-
phase voltage selection. See Figure 1-24, and
Figure 1-25 for the different configurations. Move the
selector switch to the desired position before starting the
generator set and do not switch voltage while the
generator set is running.
3PH
TP-5872-1
277/480V
3PH
120/240V
1PH
120/208V
3PH
Figure 1-24 Voltage Selector Switch, 60--200KRP
Figure 1-25 Voltage Selector Switch, 400KRP
All load voltages must match the selected voltage of the
switch. Use the voltage adjustment at the controller to
adjust the generator set output voltage.
1.6.10 Work Lights
The generator set/trailer has battery-powered work
lights and a 60-minute timer. A work light and timer
switch are available at the electrical power panel.
Activate the enclosure work lights using the timer switch
located at the back of the electrical power panel. See
Figure 1-26.
TP-5872-1
WORK LIGHTS
OFF
MINUTES
Turn-
Past
15
30
60
45
Figure 1-26 Work Lights Timer Switch