TP-6836 4/14 13Section 2 Installation
Section 2 Installation
2.1 Introduction
Kohlerr transfer switches are shipped factory-wired,
factory-tested, and ready for installation.
Have the equipment installed only be trained and
qualified personnel. The installation must comply with
applicable codes and standards.
Switch installation includes the following steps:
D Unpack and inspect the transfer switch upon receipt.
D Verify that the transfer switch voltage and frequency
ratings match the voltages and frequencies of the
sources.
D Mount the transfer switch.
D Check the manual operation.
D Connect the controller harness and ground lead.
D Connect the normal power source (utility),
emergency power source (generator set), and load
circuits.
D Connect the generator set engine start leads.
D Connect accessories, if provided.
D Check voltages and operation.
Protect the switch against damage before and during
installation.
Note: A protective device such as a molded-case circuit
breaker or fused disconnect switch MUST be
installed on both sources of incoming power for
circuit protection and used as a disconnect
device.
The functional tests in Section 6 are a necessary part of
the installation. Be sure to perform the functional tests,
which include voltage checks and operation tests,
before putting the transfer switch into service.
2.2 Receipt of Unit
2.2.1 Inspection
At the time of delivery, inspect the packaging and the
transfer switch for signs of shipping damage. Unpack
the transfer switch as soon as possible and inspect the
exterior and interior for shipping damage. If damage
and/or rough handling is evident, immediately file a
damage claim with the transportation company.
2.2.2 Lifting
Unbalanced weight.
Improper lifting can cause severe
injury or death and equipment
damage.
Use adequate lifting capacity.
Never leave the transfer switch
standing upright unless it is securely
bolted in place or stabilized.
WARNING
Figure 2-1 shows approximate transfer switch weights.
Use lifting eyes and a spreader bar to lift the transfer
switch. Ensure the front door is in place and latched
closed when moving or mounting the unit.
Number of
Poles
Amps Weight, kg (lb.)
2 150, 225, 260, 400 340 (750)
3
150, 225, 260, 400 340 (750)
600 553 (1220)
800, 1000, 1200 615 (1355)
1600, 2000 1406 (3100)
2600, 3000 1769 (3900)
4
150, 225, 260, 400 386 (850)
600 619 (1365)
800, 1000, 1200 712 (1570)
1600, 2000 1815 (4000)
2600, 3000 2268 (5000)
Figure 2-1 Approximate Weights with NEMA 1
Enclosures