TP-6836 4/14 21Section 2 Installation
2.7.3 Auxiliary Contact Connections
Terminals for field connections to the A3 Source 2
auxiliary contacts and the A4 Source 1 auxiliary
contacts are also provided. See Figure 2-9 through
Figure 2-11. These terminals are clearly marked and
are located on the side of the power panel. On 400 amp
metal frame units these terminals are located on the
bracket above the operator handle. See the transfer
switch wiring diagrams for more information.
Auxiliary Contacts
Contact Rating 15 A @ 240 VAC
1
ADV-8606
1. Engine start and auxiliary contact connections
Figure 2-9 Engine Start and Auxiliary Contacts,
150--400 Amp Models
1
ADV-8608
1. Engine start and auxiliary contact connections
Figure 2-10 Engine Start and Auxiliary Contacts,
600--1200 Amp Models