SC200 Installation& Operation Manual 3-16
6
Electrical
WARNING: Failure to comply with these regulations may cause serious injury or death
and cause damage to the machine and its surroundings.
CAUTION: Switching the machine “off” does not de-energize all circuits. Always disconnect
power before servicing.
• All KOLD-DRAFT models are intended to be installed with a permanent connection to the field
electrical supply. See rating plate on the back of the machine for power supply requirements.
• Each ice maker must be connected to a separate protected circuit with no other loads.
• Fused disconnects, installed adjacent to each ice maker, are recommended and may be
required by local codes. These components must be supplied by the installer.
• Electrical service must fall within the voltage tolerances listed below:
Maximum Overload Protection must be no greater than specified. The minimum circuit
ampacity specified does not indicate a typical running current value. Use the minimum
ampacity value for sizing branch circuit conductorsup to 26 feet (8 meters) in length. For a
conductor length over this length, increase the wire gauge as required by code.