22
Electrical installation
Operation Manual Expansion Module SO CM-E
1800.202B.0-01 Date: 02/2019
4.6.3 Power supply "Single + Dual"
The supply voltage for the axis controllers is supplied by the supply unit ServoOne CM-P
via the busbars (DC link). This voltage, also called the DC link voltage, is between
565V DC and 678 V DC, depending on the mains supply to the SO CM-P (400 V AC
and 480V AC).
The expansion module is used to protect, monitor and adapt the smaller cable cross-
section (DC link = lower current carrying capacity) of the axis controllers SO CM BG1+2
to the larger cable cross-section (DC link = higher current carrying capacity) of the axis
controllers SO CM BG3+4.
Figure Key
24 V DC Netzteil
(Power Supply)
2.
DC-Link +
DC-Link -
3.
4.
1.
X2
5. 6.
1. DC link jumper (large cross-section)
2. Controller MotionOne CM
3. Supply unit SO CM-P BG3
4. Axis controller SO CM BG3
5. Expansion module SO CM-E
6. Axis controller SO CM BG1
Note:
The DC link busbar ttings are to be tightened to a
torque of 2.1 Nm. Jumpers and screws are included in
the scope of supply and are in the accessories pack.
Figure 4.6 Busbars, power supply (DC link)
4.6.2 24 V control supply, "Dual End" model
Figure Key
5. 6.
X2
4.
4. "24 V control supply from the 1st
expansion module of type "Dual" terminal X2
5. SO CM-E expansion module "Dual End"
6. SO CM axis controller BG1
NOTE:
The 24 V DC busbar
ttings are to be tightened
to a torque of 2.1Nm.
For details and an overview, see Table 4.5
Figure 4.5 Busbars, 24 V control supply (type "Dual End")