Electrical installation
Operation Manual Expansion Module SO CM-E
1800.202B.0-01 Date: 02/2019
4.11 Expansion modules with "internal" quick shutdown in two rows
PE
L ≤ 1,5 m
Netz/Line
X2 X1
X2 X1
Linie 1
Linie 2
Schnellabschaltung/
Fast Shutdown
10
10
5
8
6a 77
6b 77
12
12
9
9
L
L
L
1,5 m
1
1
15
Netz/Line
et
et
et
et
et
tz/
t
z/
z/
z/
z
/Li
/Li
/L
/L
L
L
3
4
2
1
Key:
1. Mains lter )*
2. Mains choke )*
3. MotionOne CM )*
4. Supply unit SO CM-P BG3 )*
5. Axis controller SO CM BG3
6. a Expansion module SO CM-E row 1 ("Dual" model)
b Expansion module SO CM-E row 2 ("Dual End" model)
7. Axis controller SO CM BG1
8. PE earthing rail
9. PE connection SO CM-E = 16 mm
2
as per EN 61800-5-1
10. Series protective earth conductor connection 16 mm
2
, optionally PE strap (article no.: 1400.807.0)
can be used.
11. Connection of the supply connections (only SO CM-E.x0xx.1(2):
•24VDCfromexpansionmodulerow1toexpansionmodulerow2(X2)withstandardtwo-core
cable.
•Connectionfromexpansionmodulerow1toexpansionmodulerow2(X1)onlyusingpre-
assembled DC link cable, see Chapter A.5.2
12. Connection of "internal" quick shutdown via X7/ ES
)* See Operation Manual Supply Unit SO CM-P BG3+4
CAUTION! Risk of injury due to incorrect wiring!
Carelessness may result in injuries.
The "internal" quick shutdown is a safety feature. Make sure that all connections
have good contact and are sufciently secure (2.1Nm) that they cannot come
loose.
Figure 4.11 Connection example, expansion modules with "internal" quick shutdown in two rows