1 Supplementary Operating Manual
13 of 48
AmaControl
2301.83/04-EN
Start End Description Data type
8282 8282 Number of running times 30 - 59 min
Number to determine the quasi-percentage distribution
u 8bit
8283 8283 Number of running times 60 - 119 min
Number to determine the quasi-percentage distribution
u 8bit
8284 8284 Number of running times 120 - 300 min
Number to determine the quasi-percentage distribution
u 8bit
8285 8285 Number of running times >300 min
Number to determine the quasi-percentage distribution
u 8bit
8302 8302 Sum over lifetime: motor sensor open circuit
Alert
The following error numbers are counted: {10},{41}
u 16bit
8303 8303 Sum over lifetime: motor sensor short circuit
Alert
The following error numbers are counted: {8},{40}
u 16bit
8306 8306 Sum over lifetime: motor temperature static tripping
Alert
The following error numbers are counted: {2},{15},{38},{39},{55}
u 16bit
8307 8307 Sum over lifetime: motor temperature static tripping
Alert, interlocked
u 16bit
8316 8316 Sum over lifetime: phase loss
Alert
The following error numbers are counted: {28}
u 16bit
8317 8317 Sum over lifetime: phase loss
Alert, interlocked
u 16bit
8318 8318 Sum over lifetime: limit of frequency of starts
Alert
The following error numbers are counted: {7}
u 16bit
8319 8319 Sum over lifetime: motor detected as running even though the relay was
switched OFF
Message
The following error numbers are counted: {11},{118}
u 16bit
8320 8320 Sum over lifetime: power reset
Message
The following event numbers are counted: {1}
u 16bit
8321 8321 Sum over lifetime: successful parameter change
Message
u 16bit
8331 8331 Sum over lifetime: phase sequence error
Alert, interlocked
The following event numbers are counted: {27}
u 16bit
8334 8334 Remaining delay period
Estimated time before the motor can be switched on again
0..65533 sec
65,535 = interlocked tripping
65,534 = time undefined
u 16bit
8336 8336 Time since last fault in minutes/hours
0..120 = 0…120 min
121..238 = 3..120 h
u 8bit
8337 8337 Time since last fault in days
0 = 0 days
1…246 = 6…251 days
u 8bit
8338 8338 Sum of motor running time although the relay was switched off
Value * 10 min
u 16bit
8342 8342 Sum over lifetime: phase asymmetry detected
Warning
The following event numbers are counted: {110}
u 16bit