1 Supplementary Operating Manual
10 of 48
AmaControl
2301.83/04-EN
1.3.8 Triggering remote reset
INT 600 DM Gateway provides a volt-free changeover contact for resetting fault
messages. The relay is controlled via register dec 9735. Sequence of control
commands with (FC10) (Preset Multiple Registers): write dec 15,300 once and then
dec 42,455. The relay then switches on for 5seconds. A remote reset is possible a
maximum of 3times in 24hours and no more than oncein 30minutes. The reset
should take no longer than 5seconds. (ðSection1.5.1.1,Page46)
1.4 Modbus Protocol
1.4.1 Modbus protocol, AmaControl 3
NOTE
The AmaControl 3 Modbus registers are read using the INT 600 DM Gateway.
Table13: Modbus protocol, AmaControl 3
Start End Description Data type
8192 8192 High byte: visual ID
Low byte: reserved
u 16bit
8193 8193 High (12 bit): article main number
Low (4 bit): reserved
u 16bit
8194 8195 Consecutive serial number within the article number u 32bit
8196 8196 Ohmic value of motor temperature sensor
1-65535Ω, 0 = not available
u 16bit
8198 8198 Fault message
Bit 0: 0 = no fault, 1 = at least one fault currently present
u 16bit
8199 8199 Status message
Bit 0: motor status: 0 = motor at standstill, 1 = motor running
u 16bit
8202 8202 Motor temperature
Temperature = (value - 32768) / 100
-327.00 °C…+327.00 °C
s 16bit
8206 8206 Software revision
High byte: major software revision number
Low byte: minor software revision number
Displayed: major.minor (e.g. 1.02)
u 16bit
8207 8207 Data matrix functional variant
0 = engineering sample
1-9 = variants in ascending order
u 16bit
8210 8210 Article number variants
If value < 10000
"S" [value]
If value > 10000
"P" [value - 10000]
u 16bit
8211 8211 Voltage key
22 = Dual voltage 115-230 VAC
31 = 24 VAC
13 = 24 VDC
u 16bit
8212 8213 Total number of fault trips
0…327675
Little-endian
u 32bit
8214 8215 Total number of operational trips
0...327675
Little-endian
u 32bit
8216 8216 Number of seconds of the current hour (internal time)
0-3599 s
u 16bit