1 Supplementary Operating Manual
35 of 48
AmaControl
2301.83/04-EN
1.4.4 Modbus protocol, AmaControl L
NOTE
The AmaControl L Modbus registers are read using the INT 600 DM Gateway.
Table16: Modbus protocol, AmaControl L
Start End Description Data type
10752 10752 High byte: visual ID
Low byte: reserved
u 16bit
10753 10753 High (12 bit): article main number
Low (4 bit): reserved
u 16bit
10754 10755 Consecutive serial number within the article number
Low word first
u 32bit
10758 10758 Fault message
Bit 0: 0 = no fault, 1 = at least one fault currently present
u 16bit
10759 10759 Operating status
Bit 0 – motor status: 1 = motor running
Bit 6 – alarm relay
Bit 7 – warning relay
Bit 8 – reset input
Bit 9 – reset key
{1=active}
u 16bit
10766 10766 Software revision
High byte: major software revision number
Low byte: minor software revision number, displayed: major. minor (e.g.
1.02)
u 16bit
10767 10767 Function variant
0 = engineering sample
1-9 = variants
u 16bit
10770 10770 Article number variants
If value < 10000
"S" [value]
If value > 10000
"P" [value - 10000]
u 16bit
10771 10771 Voltage key
13 = 24VDC
20 = 24VAC/DC
22 = 115-230V AC
31 = 24VAC
41 = 115VAC
52 = 230VAC
u 16bit
10772 10773 Total number of fault trips
Low word first
u 32bit
10774 10775 Total number of pump starts
Low word first
u 32bit
10776 10776 Number of seconds of the current hour (internal time) 0-3599s u 16bit
10777 10777 Remaining delay period / Estimated time before the motor can be re-
started
0..65,533 seconds
65,535 = interlocked tripping
65,534 = time undefined
u 16bit
10778 10779 Time stamp
Seconds elapsed since 01/01/1970 00:00:00,
POSIX format
u 32bit
10780 10781 Time stamp of last switching operation as per operating routine
Seconds elapsed since 01/01/1970 00:00:00,
POSIX format
u 32bit
10788 10788 Number of hours of the current day (internal time ) 0 - 23h u 16bit