1 Supplementary Operating Manual
36 of 48
AmaControl
2301.83/04-EN
Start End Description Data type
10789 10789 Running time until service due, in hours u 16bit
10792 10792 Module condition, motor temperature
High byte: error number
Low byte: module condition, bit-coded
Bit 0 = active
Bit 1 = warning
Bit 2 = fault
Bit 3 = re-start delay
Bit 4 = interlocked
u 16bit
10793 10793 Motor temperature sensor, resistance actual value
1...65,535Ω, 0 = not applicable
u 16bit
10794 10794 Module condition, temperature 1
High byte: error number
Low byte: module condition, bit-coded
Bit 0 = active
Bit 1 = warning
Bit 2 = fault
Bit 3 = re-start delay
Bit 4 = interlocked
u 16bit
10795 10795 Temperature sensor 1, resistance actual value
1...65,535Ω, 0 = not applicable
u 16bit
10798 10798 Module condition, leakage 1
High byte: error number
Low byte: module condition, bit-coded
Bit 0 = active
Bit 1 = warning
Bit 2 = fault
Bit 3 = re-start delay
Bit 4 = interlocked
u 16bit
10799 10799 Leakage 1, resistance actual value
1...65,535 Ω, 0 = not applicable
u 16bit
10818 10818 Module condition, general monitoring
High byte: error number
Low byte: module condition, bit-coded
Bit 0 = active
Bit 1 = warning
Bit 2 = fault
Bit 3 = re-start delay
Bit 4 = interlocked
u 16bit
10828 10829 Totalled operating time
Operating time = value * 10 minutes
0...4 294 967 296minutes
Low word first
u 32bit
10830 10831 Totalled operating time with active warning
Operating time = value * 10 minutes
0...4 294 967 296minutes
Low word first
u 32bit
10834 10835 Totalled non-operating time
Operating time = value * 10 minutes
0...4 294 967 296minutes
Low word first
u 32bit
10852 10852 Motor temperature actual value
Temperature = (value - 32768) / 100 -327.00°C…+327.00°C
s 16offset
10854 10854 Temperature sensor 1, actual value
Temperature = (value - 32768) / 100 -327.00°C…+327.00°C
65535 = not available
s 16offset
10894 10895 Time since last fault in minutes u 32bit
10912 10912 Event memory: index, current event, position in rolling event memory
0...65,535
u 16bit