EasyManua.ls Logo

KSB AmaControl INT 600 DM - Page 37

KSB AmaControl INT 600 DM
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1 Supplementary Operating Manual
37 of 48
AmaControl
2301.83/04-EN
Start End Description Data type
10913 10913 Event memory: index, current measured values set
Position in rolling measured value memory
0...65 535
u 16bit
10914 10915 Event memory: last event, time stamp
0...4,294,967,295seconds elapsed since 01/01/1970 00:00:00,
POSIX format
u 32bit
10916 10916 Event memory: last event, error number u 16bit
10992 10992 Sum over lifetime:
motor temperature, static tripping
Tripping
The following error numbers are counted: {2},{15},{38},{39},{55},{79}
u 16bit
10993 10993 Sum over lifetime:
motor temperature, static tripping
Interlocked tripping
The following error numbers are counted: {2},{15},{38},{39},{55},{79}
u 16bit
10994 10994 Sum over lifetime:
motor sensor, short circuit
Tripping
The following error numbers are counted: {8},{40}
u 16bit
10995 10995 Sum over lifetime:
motor sensor, open circuit
Tripping
The following error numbers are counted: {10},{41}
u 16bit
10996 10996 Sum over lifetime:
temperature sensor 1, temperature exceeded
Tripping
The following event numbers are counted: {56},{57}
u 16bit
10997 10997 Sum over lifetime:
temperature sensor 1, temperature exceeded
Interlocked tripping
The following error numbers are counted: {56},{57}
u 16bit
10998 10998 Sum over lifetime:
temperature sensor 1, short circuit
Tripping
The following event numbers are counted: {58}
u 16bit
10999 10999 Sum over lifetime:
temperature sensor 1, open circuit
Tripping
The following event numbers are counted: {59}
u 16bit
11004 11004 Sum over lifetime:
leakage monitoring 1
Tripping
The following error numbers are counted: {64},{65}
u 16bit
11005 11005 Sum over lifetime:
leakage monitoring 1
Interlocked tripping
The following error numbers are counted: {64},{65}
u 16bit
11032 11032 Sum over lifetime:
device fault
Tripping
The following event numbers are counted: {31}
u 16bit
11074 11074 Sum over lifetime:
motor temperature exceeded
Warning
The following error numbers are counted: {122}
u 16bit
11075 11075 Sum over lifetime:
leakage monitoring 1
Warning
The following event numbers are counted: {125}
u 16bit