1 Supplementary Operating Manual
37 of 48
AmaControl
2301.83/04-EN
Start End Description Data type
10913 10913 Event memory: index, current measured values set
Position in rolling measured value memory
0...65 535
u 16bit
10914 10915 Event memory: last event, time stamp
0...4,294,967,295seconds elapsed since 01/01/1970 00:00:00,
POSIX format
u 32bit
10916 10916 Event memory: last event, error number u 16bit
10992 10992 Sum over lifetime:
motor temperature, static tripping
Tripping
The following error numbers are counted: {2},{15},{38},{39},{55},{79}
u 16bit
10993 10993 Sum over lifetime:
motor temperature, static tripping
Interlocked tripping
The following error numbers are counted: {2},{15},{38},{39},{55},{79}
u 16bit
10994 10994 Sum over lifetime:
motor sensor, short circuit
Tripping
The following error numbers are counted: {8},{40}
u 16bit
10995 10995 Sum over lifetime:
motor sensor, open circuit
Tripping
The following error numbers are counted: {10},{41}
u 16bit
10996 10996 Sum over lifetime:
temperature sensor 1, temperature exceeded
Tripping
The following event numbers are counted: {56},{57}
u 16bit
10997 10997 Sum over lifetime:
temperature sensor 1, temperature exceeded
Interlocked tripping
The following error numbers are counted: {56},{57}
u 16bit
10998 10998 Sum over lifetime:
temperature sensor 1, short circuit
Tripping
The following event numbers are counted: {58}
u 16bit
10999 10999 Sum over lifetime:
temperature sensor 1, open circuit
Tripping
The following event numbers are counted: {59}
u 16bit
11004 11004 Sum over lifetime:
leakage monitoring 1
Tripping
The following error numbers are counted: {64},{65}
u 16bit
11005 11005 Sum over lifetime:
leakage monitoring 1
Interlocked tripping
The following error numbers are counted: {64},{65}
u 16bit
11032 11032 Sum over lifetime:
device fault
Tripping
The following event numbers are counted: {31}
u 16bit
11074 11074 Sum over lifetime:
motor temperature exceeded
Warning
The following error numbers are counted: {122}
u 16bit
11075 11075 Sum over lifetime:
leakage monitoring 1
Warning
The following event numbers are counted: {125}
u 16bit