1 Supplementary Operating Manual
16 of 48
AmaControl
2301.83/04-EN
Start End Description Data type
8501 8501 Sum over lifetime: phase monitoring, overvoltage
Warning
u 16bit
8502 8502 Sum over lifetime: phase monitoring, undervoltage Alert u 16bit
8503 8503 Sum over lifetime: phase monitoring, undervoltage
Alert, interlocked
u 16bit
8504 8504 Sum over lifetime: phase monitoring, overvoltage
Alert
The following event numbers are counted: {46},{117}
u 16bit
8505 8505 Sum over lifetime: phase monitoring, overvoltage
Alert, interlocked
u 16bit
8508 8508 Motor temperature trip value
Temperature = (value - 32768) / 100
-327.00 °C…+327.00 °C
s 16bit
8554 8554 Module condition, leakage monitoring 1
High byte: error number
Low byte: module condition, bit-coded
Bit 0 = active
Bit 1 = warning
Bit 2 = fault
Bit 3 = re-start delay
Bit 4 = interlocked
u 16bit
8555 8555 Module condition, leakage monitoring 2
High byte: error number
Low byte: module condition, bit-coded
Bit 0 = active
Bit 1 = warning
Bit 2 = fault
Bit 3 = re-start delay
Bit 4 = interlocked
u 16bit
8556 8556 Module condition, phase sequence
High byte: error number
Low byte: module condition, bit-coded
Bit 0 = active
Bit 1 = warning
Bit 2 = fault
Bit 3 = re-start delay
Bit 4 = interlocked
u 16bit
8557 8557 Module condition, phase failure
High byte: error number
Low byte: module condition, bit-coded
Bit 0 = active
Bit 1 = warning
Bit 2 = fault
Bit 3 = re-start delay
Bit 4 = interlocked
u 16bit
8558 8558 Module condition, phase asymmetry
High byte: error number
Low byte: module condition, bit-coded
Bit 0 = active
Bit 1 = warning
Bit 2 = fault
Bit 3 = re-start delay
Bit 4 = interlocked
u 16bit